Setting changes, Automatic and manual generator control, Bulk and float charging parameters – Xantrex Technology power Inverter Stacking User Manual

Page 40: Equalize charging, Change the equalize charging settings as follows, Setting changes –4

Advertising
background image

Operation

3–4

975-0059-01-01 Rev A

Setting Changes

When operating a Sine Wave Plus in a series-stacked configuration, the following
settings must be changed for proper operation.

See the Owner’s Manual for the Sine Wave Plus for detailed instructions on
accessing and changing the settings using the Inverter Control Module (ICM) on
the inverter.

Automatic and Manual Generator Control

When multiple inverters are used with a generator, the inverter connected to the
generator via the Generator Start Module (GSM) is designated as the “generator
controlling” inverter. The most efficient battery charging is achieved by setting
the charging parameters of each inverter slightly differently.

Bulk and Float Charging Parameters

Change the Bulk and Float Charging settings as follows:

Set the 12B B

ULK

V

OLTS

DC to the same setting on both inverters.

Set the 12C F

LOAT

V

OLTS

DC to the same setting on both inverters.

On the non-generator-controlling inverter (the inverter not connected to a
GSM), set the charging time for a shorter period than on the generator
controlling inverter. This is accomplished by setting the 12F B

ULK

D

ONE

A

MPS

to a higher setting. If the 12F B

ULK

D

ONE

A

MPS

is set to zero (0), then

the 12H M

AX

B

ULK

/EQ Timer h:m should be set to a shorter time period on

the non-generator-controlling inverter.

Equalize Charging

Change the Equalize Charging settings as follows:

Set both inverters to the same 12D E

QUALIZE

V

OLTS

DC setting.

Set the 12G EQ V

DC

D

ONE

T

IMER

H

:

M

on the “generator controlling” inverter

to a shorter equalize time.

To start an Equalize charge (manually or automatically), set both inverters to EQ
by scrolling to 01B EQ C

HARGE

O

N

/O

FF

and selecting ON.

During the equalize charge, the Bulk LED will slowly flash on each inverter,
indicating the EQ selection has been enabled.