York YZE024 THRU 060 User Manual

Page 3

Advertising
background image

Johnson Controls Unitary Products

3

246750-YTG-L-0408

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon-

necting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the Physical and Electrical

Data Table.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evap-

orator + adder for line set.

Additional R-410A Charge / TXV Size for Various Matched Systems

Outdoor Unit

YZE02411

YZE03611

YZE04811

YZE06011

Approved System Thermal Expansion Valve

1

1TVM902

1TVM902

1TVM4A1

1TVM905

1TVM906

Factory R-410A Charge, lbs-oz

8 - 14

8 - 8

14 - 8

14 - 0

Indoor Coil

2

TXV Kit

3

- Additional Charge, Oz

FC/MC/PC/UC30A

+ 4

FC/MC/PC/UC30B

+ 4

FC/MC/PC32A

+ 6

FC/MC/PC35B

+ 6

+ 0

FC/MC/PC35C

+ 6

+ 0

FC/MC/PC/UC36A

+ 5

FC/MC/PC/UC36B

+ 5

FC/MC/PC36C

+ 5

FC/MC/PC/UC42B

+ 12

+ 0

FC/MC/PC/UC42C

+ 12

+ 0

FC/MC/PC/UC48C

+ 14

FC/MC/PC/UC48D

+ 14

FC/PC/UC60C

+ 9

+ 9

FC/MC/PC/UC60D

+ 9

+ 9

FC/MC62D

+ 17

+ 16

HC30

+ 4

HC36

+ 6

HC42

+ 12

HC60

+ 9

+ 9

HD24

HD36

+ 6

HD48

+ 10

HD60

+ 9

+ 9

AV24

+ 4

AV36

+ 12

+ 0

AV/SV48

+ 17

+ 9

AV/SV60

+ 9

+ 9

F*FV060

+ 9

+ 9

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3.

A

TXV kit must be used with these coils to obtain system performance.

Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV.

Advertising