DeviceNet Network Scanner DVPDNET-SL

8 Setup of Slave Mode

DVPDNET-SL can serve as slave through modifying of the mode by software. As DVPDNET-SL serves as slave,

the default input / output data length is 8 bytes and max input / output data length is 255 bytes.

DVPDNET-SL can be set as slave mode in the following method.

1) Connect the devices according to below figure. PC accesses PLC MPU via RS232 or RS485.

DVP28SV

DVPDNET-SL

DeviceNet Builder

2) Open DeviceNet Builder software, and select “Setup” => “Communication Setting” => “System Channel”,

and the “Serial Port Setting” dialog box will appear as below.

3)

Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud

rate and communication format. Click on “OK” after configuration is finished.

Item

Function

Default

COM Port

COM port on the PC to be used to communicate
with DVP-SV

COM1

Address

Communication address of DVP-SV

01

Baud rate

Communication speed between the PC and
DVP-SV

9,600 (bps)

Data Bits

7

Parity Even

Parity

Stop Bit

Communication protocol between the PC and
DVP-SV

1

Mode

Communication mode between the PC and
DVP-SV

ASCII

DVP-PLC Operation Manual