3M MACURCO GD-6 User Manual

Page 5

Advertising
background image

6

7

Installation
1. The 3M™ Macurco™ GD-6 Combustible Gas Detector mounts on a type 4S electrical box supplied by the contractor.
2. Connect the 3M™ Macurco™ GD-6 Combustible Gas Detector to Class 2 power supply only. It is suggested to use a

separate transformer for powering the unit or units because of possible interference’s from other devices on the same

power supply.

3. Connect the 3M™ Macurco™ GD-6 Combustible Gas Detector to the control cables with terminal plugs. When making

connections, make sure the power is off.

4. There are two terminals for Power: 12 to 24VAC or 12 to 48VDC, with no polarity preference.
5. There are two terminals for the dry alarm relay contacts, again with no polarity preference. The alarm relay can switch up

to 0.5A, 200V, or 10VA. The alarm relay is activated if gas reaches or exceeds the alarm settings.

6. The alarm relay can be configured to normally open (default) (N.O.) or normally closed (N.C.) and will activate if the gas

concentration exceeds alarm set point (5, 10, 15, 20 (default), 25% LEL). It will deactivate once the gas concentration drops

below the alarm set point. Note that the “disable” setting will cause the alarm relay not to engage at all.

7. The dry contact, SPDT fan relay has three terminals. The common (COM.), normally open (N.O.) and the normally closed

(N.C.) contact. The fan relay can switch up to 5.0A up to 240VAC. (see OPERATION section of these User Instructions for

details on relay settings).

8. The fan relay can be wired to normally open (N.O.) or normally closed (N.C.) and will engage if the fan setting (1, 2, 3,

4, 5, 6, 7, 8, 9, 10 (default), 11, 12, 13, 14, 15, 16, 17, 18, 19, 20% LEL) is exceeded for the fan relay delay time (0, 1,

3 (default), 5, 10 minutes). The fan relay will disengage once both of these conditions have been met: 1. Combustible

gas concentration has dropped below fan setting and 2. Fan relay run time (0 (default), 3, 5, 10, 15 minutes) has been

exceeded. Note that the “disable” fan setting will cause the fan relay to not engage. The fan relay will engage in trouble

fault condition and will disengage once trouble fault condition is cleared.

9. The Current Loop is 4mA in clean air and 4-20mA for 0-50% LEL.

Percent % LEL

0

12.5

25

37.5

50

4

Output in mA: GD-6

9

14

20

GD-6 rear view with

Modular Connectors

Advertising