Wiring requirements, Control and power leads, Table-3 control and power wiring data – Schneider Electric MS40-717X User Manual

Page 14: See figure-13

Advertising
background image

14

© Copyright 2010 Schneider Electric All Rights Reserved.

F-26748-6

Wiring Requirements

Control and Power Leads

Remove blue plastic thread protectors before installing conduit fittings. See Figure-1 through
Figure 8 for typical wiring applications and Table-3 for maximum wire lengths.

Caution: The 24 Vac model contains a half-wave rectifier power supply and must not be
powered by transformers used to power other devices utilizing non-isolated full-wave
rectifier power supplies. Refer to EN-206 Guidelines for Powering Multiple Full-Wave and
Half-Wave Rectifier Devices from a Common Transformer
, F-26363, for further information.

Note: Class 2 control and power lead wiring must be routed separately from line voltage
wiring and any other non-class 2 circuits.

Table-3 Control and Power Wiring Data.

Table-4 Wire Color Codes for Models Manufactured before December, 2007.

Figure-13 Installation of Universal Shaft Extension.

Actuator

Anti-rotation
Bracket
(included with
actuator)

AM-753
Universal
Mounting
Clamps

Duct

V-clamp

Mounting Surface

Damper Shaft

AM-676
Universal Shaft
Extension

1

1 The AM-676 extends the

damper shaft approximately
9" (229 mm).

Actuator

Voltage

Part

Number

Maximum Wire Run in ft. (m)

(5% Voltage Drop)

14 AWG

16 AWG

18 AWG

24 Vac and

22-30 Vdc

MS40-7173

981

(299)

617

(188)

388

(118)

120 Vac

MS40-7170

240 Vac

MS40-7171

Part Number

Power

Voltage

L1

L2

Ground

24 H

24 G

Analog

Input

500 Ohms

Common

MS40-7173-0-0-0

Old Design

24 Vac

N/A

N/A

Green/Yellow

Black

Black/Blue

White

Red

Black

MS40-7170-0-0-0

Old Design

120 Vac

Black

White

Green/Yellow

N/A

N/A

White

Red

Black

MS40-7171-0-0-0

Old Design

240 Vac

Brown

Light

Blue

Green/Yellow

N/A

N/A

White Red

Black

N/A: Not Applicable