Heating sequence of operation – Bard MD4000 User Manual

Page 10

Advertising
background image

Manual 2100-574

Page

10 of 23

MD4000

decides Lead

unit

Spyder 1 is lead

Signals Spyder2

as lag.

Spyder 2 is lead

Signals Spyder1

as Lag

DC Amp load is read and

converted to building load

with the equation DCA *

106.4-.2455 = BTUH

Calculate

Available Cooling

(AC) for 1 econ

Available cooling =( SP-

MTD-OAT)*1.08*Airflow

If AC > BL

Calculate MAT

Start Econ 1

Stop Econ 2

Stop Blower 2

Yes

No

Calculate

Available cooling

for 2 econ

If AC*2 > BL

Yes

No

Start Lead

Compressor

Start Lead Blower

No

Is OAT suitable

for Cooling

Yes

If OAT <= SP-MTD

and Enthalpy is below

curve(if equipped

Determine Building

Load

Calculate MAT

Start Econ 1

Start Econ 2

Start Blower 2

Calculate MAT

Start Econ 1

Start Econ 2

Start Blower 2

Is RT

above SP

Yes

No

Stop Lead

Compressor

Is RT

above or

below SP

No

Yes

Calculate adjusted

building Load

(BL)

MAT will be adjusted to take

into account deviation from

setpoint

BL+((RT-SP)*Airflow*1.2)

Is RT

Below SP

No

Yes

Is RT

Above ALarn

Setpoint

Yes

Start Lag

Compressor

No

Allow econ

operation with

Compressor

No

Yes

Stop Econ 1

Stop Econ 2

Stop Blower 2

Is 2

nd

comp

Allowed

Yes

NO

MD4000-BCESDC/MD4000-BESDC

W/ AC UNITS W/ DC CONTROL

ECONOMIZERS

OAT = Outdoor Air Temperature

BL = Building Load

MDT = Minimum Temperature Differential

RT = Room Temperature

SP = Setpoint

AC = Available Cooling

heatInG seQuence OF OPeratIOn

Note: All heating sequences for air conditioners with
electric heat or heat pumps will automatically operate
in Alternating Lead/Lag/Lead/Lag sequence even if
controller is set to Non-Alternating for cooling with or
without economizers.

1. Air Conditioners with Electric Heat

1

st

stage heating set point is the dead-band (db) below

the 1

st

stage cooling set point (the SP entered into the

program). The dead-band is adjustable from 2-40F, and
factory default is 27F.

2

nd

stage heating set point will operate at same inter

stage differential as set for cooling mode.