Bosch FPE-5000-UGM Interface Module User Manual

Page 13

Advertising
background image

English

F.01U.028.289

Product description FPE-5000-UGM

13 / 32

ST - FIR / PRM1 / deh

BDL-F01U028306 / A3

Functional description

The communication module is used to connect the FPA-5000 fire panel to the parent UGM 2020
security system.
The module provides two bi-directional transmission paths.

Terminal assignment

Pos.

Labelling

Connection

1

SDI 1 +

Data input +

2

SDI 1 -

Transmission

Data input -

3

SDO 1 +

Transmission

path 1

Data output +

4

SDO 1 -

Data output -

5

SDI 2 +

Data input +

6

SDI 2 -

Transmission

Data input -

7

SDO 2 +

Transmission

path 2

Data output +

8

SDO 2 -

Data output -

Technical specifications

Operating and display elements

4 bi-colour LEDs (green = transmission / yellow = fault)
1 key (LED test)

Input voltage

20 V DC–30 V DC (min–max) / 5 V DC

±5 %

Maximum current consumption

- Standby operation
- One transmission path active
- Both transmission paths active

7 mA (at 24 V DC)

10 mA (at 24 V DC)
13 mA (at 24 V DC)

Maximum line length

1000 m

Maximum line resistance

70

Ω

Baud rate

9600 bit/s for 1000 m – . . 38400 bit/s for 200 m

Protection class

IP 30 / EN 60529

Safety class

II in accordance with IEC 60950 / EN 60950

EMC immunity

EN 50130-4 / FCC Part 15

EMC emission

EN 61000-6-3 / FCC Part 15

Permissible operating temperature

-5 _C . . . 50 _C

Permissible storage temperature

-20 _C . . . 60 _C

Permissible relative humidity

max. 95%, non-condensing

Housing material and colour

ABS plastic (UL94 V-0), satin finish, anthracite, RAL 7016

Dimensions (h x w x d)

approx. 110 x 90 x 60 mm

Weight

approx. 150 g

1 2

3 4

5 6 7 8

Advertising