Bosch FPP-5000 External Power Supply Unit Kit 24 V User Manual

Page 11

Advertising
background image

UPS 2416 A

en | 11

F.01U.003.349 | 6.0 | 2009.03

Bosch Sicherheitssysteme GmbH

Functional description

The UPS 2416 A in plug-in design with rack and panel
connector is a universal single output power supply
unit for the FPA fire detection system.
-

The module is protected against overvoltage and
reverse polarity.

-

The output voltage is externally monitored and
regulated.

-

The green onboard LED indicates the power supply
is working (DC output).

-

In the case of a mains failure or failure of the DC
output voltage, the output at terminal FAULT (Pos.6)
drops to 0 V.

Pos.

Marking

Connection

1

ACL

AC Mains supply

2

ACN

3

Protective ground

4

DC+

26 V DC . . . 29 V DC Output plus

5

DC-

0 V DC Output minus

6

FAULT

Power fault

7

RTH+

Temperature sensor plus

8

RTH-

Temperature sensor minus

Use the power supply unit only in the
purpose-designed

power

supply

brackets and a fire enclosure (e.g. panel
housing)!

Technical specification

Input voltage (min - max)

100 V AC . . . 240 V AC (min - max)

Input frequency

50 Hz . . . 60 Hz

Current consumption

1.95 A max.

Efficiency factor

> 85 %

Hold up time

> 16 ms at 115 V AC

Output voltage

26 V DC . . . 29 V DC

Maximum load

6 A

Continious output power

160 W

Cooling

Convection without fan

Protection class as per IEC 60950 / EN 60950

I

Permissible operating temperature

-5 _C . . . 50 _C

(23 _F . . . 122 _F)

Permissible storage temperature

-20 _C . . . 60 _C

(-4 _F . . . 140 _F)

Permissible relative humidity

max. 95% non condensing

Housing material

Aluminium, anodized

Housing color

Semi gloss black

Dimensions (H x W x D)

approx. 200 x 100 x 40 mm

Weight

approx. 780 g

1 2 3 4 5 6 7 8

LED

1

8

Advertising