Power-Sonic PSX12-130 User Manual

Psx series, Vrla 10yr design life at 20 ) ºc

Advertising
background image

PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-130 12V 130AH

Nominal Voltage

Nominal Capacity

12V

130 AH

Dimension

Length

Width

Container Height

Height to top of terminal

Weight

Standard Terminal

T11

Approx 37.6kg

410

177

225

211

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

Con

s

tant

V

ol

tage

Char

ge

Recommended Charge
Current less than 32.5A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

Approx 4.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 02/13

-

(VRLA 10yr Design Life at 20

)

ºC

Power

Rating

3hr to(1.67V/cell)

1hr to(1.67V/cell)

15min to(1.67V/cell)

403.92 Watts

1035.96 Watts

2903.04 Watts

225

2

177

2

21

1

2

410

2

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

F.V(V/cell)

15min

1H

3H

1.85

192.55

77.60

30.26

1.80

219.32

81.87

31.91

1.75

239.49

85.65

32.50

1.70

255.69

88.37

33.47

1.67

271.89

91.37

34.92

1.60

290.81

94.58

35.89

F.V(V/cell)

15min

1H

3H

1.85

359.29

149.57

59.46

1.80

403.71

157.14

62.27

1.75

435.53

163.64

63.24

1.70

458.52

168.20

64.89

1.67

483.84

172.66

67.32

1.60

508.86

177.80

69.06

310

2

20

M8

6

Torque 11.0 -14.7 Nm

T11 Threaded Insert 8mm Stud

Advertising