PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-6 12V 6.0AH

Nominal Voltage

Nominal Capacity

12V

6.0 AH

Dimension

Length

Width

Container Height

Total Height (with terminal)

Weight

Standard Terminal

F2

Approx 1.80kg

90

70

101

107

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

Co

nst

a

n

t V

ol

tag

e

C

ha

rg

e

Recommended Charge
Current less than 1.5A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

6.35

7.95

3.4

0.8

F2

Approx 25.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 - 02/13

-

(VRLA 6yr Design Life at 20°C)

-

+

90

2

72 2

101

2

107

2

70

2

Power

Rating

3hr Rate(1.67V/cell)

1hr Rate(1.67V/cell)

15min Rate(1.67V/cell)

18.24 Watts

43.32 Watts

122.22 Watts

Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

F.V(V/cell)

15min

1H

3H

1.85

8.40

3.20

1.37

1.80

9.22

3.42

1.43

1.75

10.09

3.58

1.47

1.70

10.77

3.69

1.51

1.67

11.45

3.82

1.58

1.60

12.03

3.95

1.63

F.V(V/cell)

15min

1H

3H

1.85

15.71

6.18

2.68

1.80

16.98

6.56

2.78

1.75

18.33

6.84

2.85

1.70

19.30

7.03

2.92

1.67

20.37

7.22

3.04

1.60

21.05

7.43

3.11