Power-Sonic PSX12-13 User Manual

Psx series, Vrla 6yr design life at 20 ) ºc

Advertising
background image

PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-13 12V 13AH

Nominal Voltage

Nominal Capacity

12V

13 AH

Dimension

Length

Width

Container Height

Total Height (with terminal)

Weight

Standard Terminal

F2

Approx 4.2kg

151

98

95

101

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

C

ons

tant

V

o

lta

ge

C

ha

rge

Recommended Charge
Current less than 3.25A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

6.35

7.95

3.4

0.8

F2

Approx 14.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 02/13

-

(VRLA 6yr Design Life at 20

)

ºC

98

2

151

2

80

2

101

2

+

-

Power

Rating

3hr to(1.67V/cell)

1hr to(1.67V/cell)

15min to(1.67V/cell)

39.06 Watts

96.06 Watts

298.56 Watts

Constant Power Discharge Characteristics Unit: W atts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

F.V(V/cell)

15min

1H

3H

1.85

20.56

7.11

2.87

1.80

22.50

7.59

3.03

1.75

24.64

7.94

3.15

1.70

26.29

8.19

3.27

1.67

27.94

8.47

3.38

1.60

29.39

8.77

3.48

F.V(V/cell)

15min

1H

3H

1.85

38.32

13.68

5.63

1.80

41.52

14.55

5.90

1.75

44.81

15.13

6.11

1.70

47.14

15.62

6.33

1.67

49.76

16.01

6.51

1.60

51.31

16.49

6.67

95

2

Advertising
Table of contents