Power-Sonic PHR-12400 User Manual

430 w/cell, Hr. rate, Min. rate

Advertising
background image

Physical Dimensions: in (mm)

Features

• Superb high-rate discharge characteristics that ensure reliable

performance in UPS applications for up to 10 years. UL recognized

• Flame retardant ABS case and cover to UL 94 V-O for superior

performance

• VRLA Absorbent Glass Mat (AGM) Technology guarantees safe

operation without maintenance and “non-restricted article” status for

transportation. Approved for transport by air. D.O.T., I.A.T.A. and

F.A.A. certified.

• Precision plate pasting for higher consistency with 100% load

testing to ensure uniform capacity

• Patented dual-paste process for enhanced active material bonding,

and computer guided volumetric electrolyte control for precision

filling

• Lead-calcium alloy grids and the use of high purity lead account for

superior shelf-life characteristics

Performance Specifications

Nominal Voltage ............................................... 12 volts (6 cells)

Nominal Power (15 min.) .....................................430 W/Cell

Rated Capacity

20-hr. (5.50A to 10.80 volts) .................................... 110.0 AH

10-hr. (10.70A to 10.50 volts) .................................. 107.0 AH

8-hr. (12.90A to 10.50 volts) .................................. 103.2 AH

Approximate Weight .................................. 69.2 lbs. (31.4 kg)

Internal Resistance (approx.) ............................. 3.6 milliohms

Max Discharge Current (5 Sec.) ....................... 1650 amperes

Operating Temperature

Discharge ........................................... -15 ~ 50°C (5 ~ 122°F)

Charging ............................................. 0 ~ 40°C (32 ~ 104°F)

Storage .............................................. -15 ~ 40°C (5 ~ 104°F)

Maximum Charging Current ........................................ 33.0 A

Case

........................... Flame Retardant ABS Plastic (UL 94 V-O)

PHR-12400

L: 12.81(326) W: 6.69 (170) H: 8.39 (213) HT: 8.50 (216)

12 Volt 110 AH

@ 20-hr. rate

430 W/Cell

@ 15-min. rate

Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions.

www.power-sonic.com

To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.

All data subject to change without notice.

Constant Current Discharge (Amperes) at 25ºC

Constant Power Discharge (Watts/Cell) at 25ºC (Blue)

HT

H

W

L

020

M6

3

PHR-12400

5 min

10 min

15 min

20 min

30 min

45 min

1h

2h

3h

4h

5h

6h

8h

10h

20h

1.85V

216.5

183.3

159.3

136.4

104.9

76.9

61.6

35.8

26.4

21.2

17.8

15.4

12.3

10.3

5.38

1.80V

264.0

210.3

176.9

149.5

112.4

82.9

65.6

37.7

27.6

22.0

18.5

15.9

12.6

10.5

5.50

1.75V

297.0

230.3

193.6

161.7

119.7

86.8

68.9

39.5

28.7

22.6

18.8

16.3

12.9

10.7

5.63

1.70V

335.3

254.1

209.9

173.9

128.0

91.8

72.5

41.1

29.6

23.2

19.3

16.6

13.2

10.9

5.72

1.67V

363.0

275.2

227.0

186.8

135.3

96.5

75.9

42.4

30.4

23.8

19.8

17.0

13.5

11.1

5.82

1.60V

390.7

298.7

243.3

198.3

142.6

100.3

78.4

43.8

31.2

24.6

20.3

17.5

13.8

11.3

5.98

1.85V

421.2

358.6

313.4

269.7

208.5

153.4

123.4

71.9

53.3

42.9

36.1

31.4

25.2

21.2

11.1

1.80V

508.2

407.2

344.5

292.7

221.4

164.2

130.4

75.5

55.4

44.4

37.4

32.3

25.8

21.5

11.3

1.75V

565.9

441.9

373.7

313.9

233.7

170.6

136.0

78.5

57.2

45.3

37.8

32.8

26.2

21.8

11.5

1.70V

631.6

482.1

400.4

334.0

247.6

178.7

142.0

81.1

58.7

46.2

38.4

33.3

26.6

22.1

11.6

1.67V

678.3

518.2

430.4

356.5

260.1

186.8

148.0

83.2

60.0

47.2

39.2

33.8

26.9

22.3

11.8

1.60V

721.9

556.4

456.5

374.9

271.3

192.4

151.4

85.1

61.1

48.2

40.0

34.5

27.3

22.5

12.0

Advertising