Power-Sonic PSX12-6.5s User Manual

Psx series, Vrla 6yr design life at 20 ) ºc

Advertising
background image

PSX Series

Designed for UPS Applications

Discharge Characteristics (25ºC, 77ºF)

Physical Specification

Internal Resistance mΩ

Dimensions (mm)

Standard terminal (mm)

PSX12-6.5S 12V 6.5AH

Nominal Voltage

Nominal Capacity (20HR)

12V

6.5 AH

Dimension

Length

Width

Container Height

Total Height (with terminal)

Weight

Standard Terminal

F1 (Neg.) F2 (Pos.)

Approx 2.10kg

151

51

92

98

2 mm

2 mm

2 mm

2 mm

+

-

+

-

+

+

-

Capacity

Affected by

Temperature

Standby

C

o

ns

ta

nt

V

ol

tage

C

har

ge

Recommended Charge
Current less than 1.85A
Voltage 13.5V ~
13.8V at 25°C (77°F)

40°C (104°F)

25°C (77°F)

0°C (32°F)

103%

100%

86%

Approx 35.0 mΩ

Power-Sonic Europe Limited

3 Buckingham Square, Wickford, Essex, SS11 8YQ

Tel: +44 (0)1268 560686 Fax: +44 (0)1268 560902

[email protected]

www.power-sonic.co.uk

Rev3 02/13

-

(VRLA 6yr Design Life at 20

)

ºC

92

2

98

2

+

-

151

2

26

2

51

2

Power

Rating

3hr to(1.67V/cell)

1hr to(1.67V/cell)

15min to(1.67V/cell)

20.46 Watts

49.50 Watts

151.92 Watts

4.75 / 6.35

6.35 / 7.95

3.2 / 3.4

0.8

F1 / F2

Constant Power Discharge Characteristics Unit: Watts / Cell (25ºC, 77ºF)

Constant Current Discharge Characteristics Unit: Amperes (25ºC, 77ºF)

In the event of further technical development we reserve the right to alter our design, specification and price without notice. E&O.E

F.V(V/cell)

15min

1H

3H

1.85

10.48

3.67

1.58

1.80

11.45

3.91

1.62

1.75

12.51

4.09

1.65

1.70

13.39

4.22

1.70

1.67

14.26

4.37

1.78

1.60

14.94

4.52

1.82

F.V(V/cell)

15min

1H

3H

1.85

19.50

7.07

3.10

1.80

21.15

7.50

3.16

1.75

22.80

7.81

3.21

1.70

24.06

8.03

3.29

1.67

25.32

8.25

3.41

1.60

26.19

8.50

3.50

Advertising