Physical Dimensions: in (mm)

Features

• Superb high-rate discharge characteristics that ensure reliable

performance in UPS applications for up to 10 years. UL recognized

• Flame retardant ABS case and cover to UL 94 V-O for superior

performance

• VRLA Absorbent Glass Mat (AGM) Technology guarantees safe

operation without maintenance and “non-restricted article” status for

transportation. Approved for transport by air. D.O.T., I.A.T.A. and

F.A.A. certified.

• Precision plate pasting for higher consistency with 100% load

testing to ensure uniform capacity

• Patented dual-paste process for enhanced active material bonding,

and computer guided volumetric electrolyte control for precision

filling

• Lead-calcium alloy grids and the use of high purity lead account for

superior shelf-life characteristics

Performance Specifications

Nominal Voltage ............................................... 12 volts (6 cells)
Nominal Power (15 min.) .......................................93 W/Cell
Rated Capacity
20-hr. (1.35A to 10.80 volts) ...................................... 27.0 AH
10-hr. (2.66A to 10.50 volts) ...................................... 26.6 AH
8-hr. (3.22A to 10.50 volts) ...................................... 25.8 AH
Approximate Weight .................................... 17.4 lbs. (7.9 kg)
Internal Resistance (approx.) ................................. 10 milliohms
Max Discharge Current (5 Sec.) ........................... 540 amperes
Charging Voltage @ 77°F (20° C)
Standby Use
............. 2.275 ± 0.025 V/Cell, (-3.3mV/°C/Cell)
Cycle Use .......................... 2.45±0.05 V/Cell, (-5 mV /°C/Cell)
Maximum Charging Current .......................................... 8.1 A
Case .................................. Flame Retardant ABS Plastic (UL 94 V-O)

PHR-12100

www.power-sonic.com

To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.

All data subject to change without notice.

L: 6.46 (164) W: 4.92 (125) H: 6.89 (175) HT: 6.50 (165)

12 Volt 27 AH

@ 20-hr. rate

93 W/Cell

@ 15-min. rate

Constant Current Discharge (Amperes) at 25ºC

Constant Power Discharge (Watts/Cell) at 25ºC (Blue)

HT

H

W

L

M5

3

012

PHR-12100

5 min

10 min

15 min

20 min

30 min

45 min

1h

2h

3h

4h

5h

6h

8h

10h

20h

1.85V

62.5

47.7

39.0

33.0

25.7

19.5

15.8

9.40

6.86

5.44

4.51

3.88

3.05

2.54

1.32

1.80V

71.2

52.8

42.2

34.9

27.2

20.6

16.8

9.88

7.12

5.61

4.67

4.01

3.15

2.61

1.35

1.75V

81.1

56.4

44.8

37.3

28.3

21.3

17.3

10.20

7.32

5.74

4.75

4.08

3.22

2.66

1.38

1.70V

89.1

60.3

46.8

38.6

29.2

21.9

17.7

10.40

7.47

5.88

4.87

4.19

3.29

2.71

1.40

1.67V

94.8

63.0

48.9

40.1

30.1

22.5

18.2

10.60

7.62

5.98

4.98

4.28

3.34

2.75

1.43

1.60V

98.5

65.1

50.5

41.5

31.1

23.0

18.6

10.80

7.76

6.12

5.10

4.37

3.41

2.81

1.47

1.85V

121.5

93.3

76.8

65.3

51.0

38.9

31.7

18.9

13.9

11.0

9.18

7.91

6.26

5.22

2.74

1.80V

137.1

102.2

82.2

68.4

53.6

40.8

33.4

19.8

14.3

11.3

9.45

8.13

6.42

5.33

2.77

1.75V

154.5

108.1

86.6

72.3

55.3

41.7

34.1

20.2

14.6

11.5

9.55

8.23

6.52

5.42

2.82

1.70V

167.8

114.3

89.2

74.2

56.6

42.6

34.8

20.5

14.8

11.7

9.72

8.39

6.61

5.47

2.85

1.67V

177.1

118.7

92.8

76.3

57.9

43.4

35.5

20.8

15.0

11.8

9.89

8.53

6.70

5.54

2.89

1.60V

181.9

121.3

94.8

78.2

59.3

44.0

35.9

21.0

15.2

12.0

10.0

8.62

6.77

5.61

2.94

Advertising