Veris Industries HWS SERIES Datasheet User Manual

Independent rh, temp, and analog setpoint outputs, Ht/hws series, Setp oint de vices

Advertising
background image

setp

oint de

vices

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

APPLICATIONS

Hospitals and operating rooms, pharmaceutical labs

Clean rooms

Food processing plants

Environmental testing facilities, and other institutional applications

FEATURES

Independent RH and T (HT relay) or analog setpoint outputs (HT analog)

provide application flexibility

LCD for local display of readings and setup values

Offset function adjusts calibration intervals for both RH and T (HT models)

Switch-selectable 4-20mA or 0-10V/0-5VDC analog outputs

Multi-point calibration to 1% RH, traceable to NIST

Replaceable RH sensor element supports field calibration offset...saves time

Semiconductor temperature sensor can be field calibrated

Independent RH, Temp, and

Analog Setpoint Outputs

Wall Mount Humidity

Transmitter Thermostat

Humidistat Functions

DESCRIPTION

All HT/HWS Series institutional grade relative humidity/temperature transmitters

are designed to meet the rigorous needs of pharmaceutical labs, hospitals, science

labs, and other settings that call for precise environmental control. Internal jumpers

control access to a feature that allows adjustment of the calibration offsets. The

devices can also be made tamper resistant using a jumper to disable keypad

programing functions. HT/HWS models are calibrated with NIST traceable

calibration equipment.

Analog Output Transmitter

Analog output models feature a keypad to make adjusting humidity and

temperature setpoint values easy. They transmit the setpoint values back to a control

system by means of dual outputs. A slide-switch allows easy selection of output

type, either 4-20mA or 0-5V/0-10VDC signals. Dual outputs enable effortless control

of both humidity and temperature in a single, compact sensor.

Setpoint Relay Transmitter

The HT Series setpoint relay models also offer thermostat or humidistat functionality.

Two separate relays can be configured to control heating and cooling when in

thermostat mode, or humidifying and de-humidifying when in humidistat mode.

HWS models offer the same precise humidity measurement and control as the HT,

but without the temperature and thermostat features.

SPECIFICATIONS

Input Power

15 to 30VDC/24VAC, 100mA max.

Outputs, Analog

Switch-selectable 4-20mA, or 0-10V/0-5VDC (switch affects both outputs)

Outputs, Relay (Relay models only)

2 Form C (SPDT), 1A 30VDC, resistive, 30W max.

HS Element

Digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138†

Accuracy at 25°C from 10-80% RH* (Multi-point calibration NIST traceable)

±2%, 3%, or 5% models ; ±1% at 20-50% RH on HTA models

±1% at 12-40% RH on HTR models in mA output mode; ±1% at 30% RH on HTR models in voltage output mode

Reset Rate**

24 hours

Stability

±1% @ 20°C (68°F) annually, for two years

Hysteresis

RH: 1.5% (typical), Temp: 1° to 10°F in 1°F increments

Linearity

Included in accuracy spec.

Operating Humidity Range

0-100% RH non-condensing

Temperature Coefficient

± 0.1%RH/°C above or below 25°C (typical)

Operating Temperature Range

10° to 35°C (50° to 95°F)

Temperature Accuracy

±1.0°C (±1.8°F)

Scaling

RH: 0-100%; Temp: 10°to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F) menu selectable

Calibration Offset

RH: Adjustable ±10% in 0.1% increments; Temp: Adjustable ±10° in 0.1° increments

Setpoint Range

RH: 10-80% in 1% increments; Temp: minimum to full scale in 1°F increments

† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.

* Specified accuracy with 24VDC supplied power with rising humidity

**Reset Rate is time required to recover to 50% RH after exposure to 90% RH for 24 hours

One side of transformer secondary is connected to signal common, so an isolation transformer or dedicated power supply may be required.

RTD/Thermistors in wall packages are not compensated for internal heating of product.

HT

HT/HWS SERIES

HQ0001872.B 01131