Veris Industries HW SerieS Install User Manual

Hw series, Notice, Installation guide

Advertising
background image

Z202638-0W

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07123

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

EnvironmEntal SEnSorS

inStallation GUiDE

Digital RH & RH/T Thermistor/RTD/Temp

Transmitter (Non-Display Model)

Installer’s Specifications

HS Element

Digitally profiled thin-film capacitive (32 bit mathematics)

U.S.

Patent 5,844,138

Accuracy at 25°C from 10-80% RH**

Multi-point calibration; NIST traceable

±2%, 3%, or 5% models

±1% at 12-60% RH in voltage output mode

±1%

at 20-40% RH in mA output mode

±1%

at 12-60% RH in mA output mode with temp transmitter

Reset Rate*

24 hours

Stability

±1%@20°C (68°F) annually, for two years

Hysteresis

1.5% (typical)

Linearity

Included in Accuracy spec.

Operating Humidity Range

0 to 100% RH

Operating Temperature Range

10°C to 35°C (50°F to 95°F)

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Analog Output

4-20 mA mode: 2-wire, polarity insensitive

0-5V/0–10

V mode: 3-wire, observe polarity

Scaling

0-100% RH

Input Power

4-20 mA mode: loop powered 12-30 VDC only, 30 mA max.

0-5V/0-10

V mode: 12-30 VDC/24 VAC, 15 mA max.

Optional Temperature Output:

Transmitter Models

Digital, 4-20mA/0-5/0-10V output, accuracy ±0.5°C (±0.9°F) typical

RTD Models

Customer specified thermistor or RTD

EMC Conformance: EN61000-6-3:2007 and A1:2011, EN61000-6-1:2007

One side of transformer secondary is connected to signal common. Isolation transformer or

dedicated power supply may be required. To conform to EMC standards, shielded cabling and

technical information is available from the factory upon request or is available on our website:

www.veris.com

* Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.

** Specified accuracy with 24 VDC supplied power with rising humidity.

RTD/Thermistors in wall packages are not compensated for internal heating of product.

HW SerieS

HW SerieS

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

ProDuct iDentification

quick install

1. Mount the sensor on a vertical wall, about 4½ feet above the floor, in a location

away from ventilation sources.

2. Affix the backplate to the wall.

3. Wire the device. Refer to wiring diagrams on page 2.

4. Install the cover.

3.50"

(89 mm)

4.75"

(121 mm)

1.15"

(29 mm)

NIST US or EU

Temp.

Sensor Type

Display Accuracy

N = NIST
X = No

S = Standard
C = CE

A = Transmitter: 10°-35°C
(50°-95°F) or 0°-50°C
(32°-122°F) (switchable)
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor

K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor
U = 20k, “D” Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor

1 = 1%
2 = 2%
3 = 3%
5 = 5%

= No display

HW

T = Temp
X = No Temp
(Stop here)

X

Temp. Cal. Cert. Option

Value

X = No Cert.
1 = 1 pt cal.
2 = 2 pt cal.

1 = Pushbutton Override
2 = Setpoint Slider
3 = Pushbutton Override
and Setpoint Slider

A = 1k
F = 10k
G = 20k
K = 50k
M = 100k

available