Veris Industries H11D Install User Manual

Danger, H11d, Notice

Advertising
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Z206073-0C

PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

01131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat,Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Switch,

Auto Calibration With Display

SPECIFICATIONS

Sensor Power

Induced from monitored current

Amperage Range

60 Hz: 2.5 - 200A max.

50

Hz: 3.0 - 200A max.

Status Output

N.O. when device is unpowered, 1.0A@30VAC/DC

not

polarity sensitive

Response Time

1 sec.

Accuracy

±

2% of full scale

Frequency Range

50/60 Hz

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

LCD Backlight

Off at low currents; illuminates when monitored current exceeds 4.5A;

flashes

during an alarm state while current remains above 4.5A

On-State Resistance

≤1.0 Ω

Off-State Resistance

≥1.0 MΩ

Setpoint Target Range, Switch Setting A*

±40% of learned nominal current;

max.

learned current of 142A to enable an upper trip limit at or below 200A

Setpoint Target Range, Switch Setting B*

±60% of learned nominal current;

max.

learned current of 125A to enable an upper trip limit at or below 200A

Switch Setting C*

On/Off Status; contacts are closed while amperage is above 2.5A

Alarm Reset Range

±

5% of learned nominal current **

Setpoint Calibration Learn Period

30 sec.; self-learning, pushbutton reset

Normal-to-Alarm Output Delay

1 sec. maximum

Alarm-to-Normal Output Delay

30 sec. nominal

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Terminal Block Wire Size

24 to 14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

CE EN 61010-1:2001, UL508, Installation Category III, pollution degree 2

* Trip point switch positions A and B are not for use in applications where the current will fluctuate

by more than 40% (A) or 60% (B) of the nominal current. If the current will fluctuate by more

than 60%, use the H11D for on/off status (position C) only.

** The upper trip limit alarm resets when the current drops by 5% of the learned nominal current.

The lower trip limit alarm resets when the current rises by 5% of learned nominal current.

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001.

Listed for use with 75°C insulated conductors.

The product design provides for basic insulation only.

Do not use the LCD as evidence of applied voltage.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

WIRING EXAMPLE

H11D

TM

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

Fan or Pump

CONTROLLER

Digital

Input

MOTOR

Insulated Conductor

CONTACTOR

INSTALLATION

Disconnect power to the enclosure containing the

conductor to be monitored.

1. Determine normal operating conditions for the application, and move the slide

switch to the best setpoint range (A, B, or C) for these conditions (e.g., if normal

operation, including duct opening/closing and filter blockage is 50% of the

learned nominal current, then set the slide switch to the B range (±60%), or use

the C range (on/off status) to indicate when current falls below 2.5A at 60 Hz). For

most blower systems, the 40% (A) setting is appropriate.

2. Locate a mounting surface for the removable mounting bracket that allows the

monitored conductor to pass through the center window when it is installed and

that keeps the product at least ½” from any uninsulated conductors. Determine

cable routing for the controller connection, allowing wiring to reach the mounting

location.

3. Drill holes and mount the bracket to the chosen surface using the included screws.

4. Wire the output connections between the sensor and the controller (solid-state

contact).

5. Verify that the core mating surfaces are clean. Snap the sensor over the conductor

and clip the assembly to the mounting bracket.

6. Secure the enclosure and reconnect power.