Veris Industries HS Install User Manual

Hs sensor replacement

Advertising
background image

TM

HS SENSOR

REPLACEMENT

Z205266-0B

08113

The microprocessor-profiled
capacitive HS element can be
replaced in the field without
calibration.

PRODUCT IDENTIFICATION

Accuracy

NIST

N = NIST (1% and

2% models only)

X = None (2%, 3%,

and 5% models

only)

1 = 1%*

2 = 2%

3 = 3%

5 = 5%

HS

X

INSTALLATION

For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connectors.

Humidity Outdoor and Duct Units

1. Disconnect power to the unit.

2. Remove probe from junction box by loosening black

swage nut and sliding out.

3. Unscrew filter on tip of probe. Set filter aside.

4. Remove HS element by gently pulling from pin

connector. Do not attempt to remove temperature

sensor adjacent to HS element (if equipped).

5. Place new HS element onto pin connector. Orient as

shown, or unit will not function (filter will not screw

on if HS is inserted incorrectly).

6. Replace filter. Re-insert probe into junction box and

tighten swage nut.

HS sensor elements are sold as open devices.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

Temp sensor
(if equipped)

Top

Side

Bottom

Side

Top

Side

Bottom

Side

TM

HS SENSOR

REPLACEMENT

Z205266-0B

08113

The microprocessor-profiled
capacitive HS element can be
replaced in the field without
calibration.

PRODUCT IDENTIFICATION

Accuracy

NIST

N = NIST (1% and

2% models only)

X = None (2%, 3%,

and 5% models

only)

1 = 1%

2 = 2%

3 = 3%

5 = 5%

HS

X

INSTALLATION

For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connectors.

Humidity Outdoor and Duct Units

1. Disconnect power to the unit.

2. Remove probe from junction box by loosening black

swage nut and sliding out.

3. Unscrew filter on tip of probe. Set filter aside.

4. Remove HS element by gently pulling from pin

connector. Do not attempt to remove temperature

sensor adjacent to HS element (if equipped).

5. Place new HS element onto pin connector. Orient as

shown, or unit will not function (filter will not screw

on if HS is inserted incorrectly).

6. Replace filter. Re-insert probe into junction box and

tighten swage nut.

HS sensor elements are sold as open devices.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

Temp sensor
(if equipped)

Top

Side

Bottom

Side

Top

Side

Bottom

Side

TM

HS SENSOR

REPLACEMENT

Z205266-0B

08113

The microprocessor-profiled
capacitive HS element can be
replaced in the field without
calibration.

PRODUCT IDENTIFICATION

Accuracy

NIST

N = NIST (1% and

2% models only)

X = None (2%, 3%,

and 5% models

only)

1 = 1%

2 = 2%

3 = 3%

5 = 5%

HS

X

INSTALLATION

For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connectors.

Humidity Outdoor and Duct Units

1. Disconnect power to the unit.

2. Remove probe from junction box by loosening black

swage nut and sliding out.

3. Unscrew filter on tip of probe. Set filter aside.

4. Remove HS element by gently pulling from pin

connector. Do not attempt to remove temperature

sensor adjacent to HS element (if equipped).

5. Place new HS element onto pin connector. Orient as

shown, or unit will not function (filter will not screw

on if HS is inserted incorrectly).

6. Replace filter. Re-insert probe into junction box and

tighten swage nut.

HS sensor elements are sold as open devices.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

Temp sensor
(if equipped)

Top

Side

Bottom

Side

Top

Side

Bottom

Side

TM

HS SENSOR

REPLACEMENT

Z205266-0B

08113

The microprocessor-profiled
capacitive HS element can be
replaced in the field without
calibration.

PRODUCT IDENTIFICATION

Accuracy

NIST

N = NIST (1% and

2% models only)

X = None (2%, 3%,

and 5% models

only)

1 = 1%

2 = 2%

3 = 3%

5 = 5%

HS

X

INSTALLATION

For all unit types, ensure that the four HS pin holes are
inserted fully onto the unit pin connectors.

Humidity Outdoor and Duct Units

1. Disconnect power to the unit.

2. Remove probe from junction box by loosening black

swage nut and sliding out.

3. Unscrew filter on tip of probe. Set filter aside.

4. Remove HS element by gently pulling from pin

connector. Do not attempt to remove temperature

sensor adjacent to HS element (if equipped).

5. Place new HS element onto pin connector. Orient as

shown, or unit will not function (filter will not screw

on if HS is inserted incorrectly).

6. Replace filter. Re-insert probe into junction box and

tighten swage nut.

HS sensor elements are sold as open devices.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

Temp sensor
(if equipped)

Top

Side

Bottom

Side

Top

Side

Bottom

Side

* 1% HS sensors used in outdoor
applications are limited by the
device to 2% accuracy.

* 1% HS sensors used in outdoor
applications are limited by the
device to 2% accuracy.

* 1% HS sensors used in outdoor
applications are limited by the
device to 2% accuracy.

* 1% HS sensors used in outdoor
applications are limited by the
device to 2% accuracy.

Advertising