Veris Industries HEW SEriES Datasheet User Manual

Standard wall humidity sensors, 2%, 3%, and 5% accuracies, Hew series

Advertising
background image

HU
MIDIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

HEW

2%, 3%, and 5% Accuracies

Year

Warranty

1

FEATURES

Monitor humidity and temperature with a single device...reduces installation

costs

Semiconductor, temperature transmitter, or popular thermistor/RTD

sensors available

Housing is low-profile...perfect for schools and museums

Standard Wall

Humidity Sensors

DESCRIPTION

HEW Standard Series wall mount humidity transmitters offer high performance in an
easy to install housing at an affordable price. The thin-film capacitive sensor element
provides high accuracy and performance, great long-term stability, and full recovery
from saturation. Temperature sensing options are also available.

The wall housing was created using sophisticated thermal analysis techniques for
optimum airflow. It is ideal for schools and other applications requiring exceptional
durability and a discrete appearance. All Standard models come with a standard
one-year warranty.

APPLICATIONS

HVAC economizer control

Managing energy systems

Facilitating ASHRAE standards for environmental control

SPECIFICATIONS

Input Power:

Input Power, Voltage Version

12-24VDC or 24VAC

Input Power, mA Version 12-24VDC

AC Voltage Tolerance ±10%

AC Frequency

50-60 Hz

Max. Inrush Current after 1 msec (mA version) 25mA

Output Power:

mA Output

4-20mA, 2-wire, not polarity sensitive

mA Max. Loop Resistance

500Ω at 24VDC input voltage; 250Ω at 12VDC input voltage

Voltage Output

0-5V or 0-10V (jumper selectable)

Voltage Min. Load Resistance 5kΩ

Voltage Min. Sinking Current 0.2mA

Humidity:

RH Element

Digitally profiled thin-film capacitive, non-removable

Accuracy

±2%, 3%, or 5% (10-90% RH, 20° to 30°C)

Temperature Effect (Outside 20° to 30°C)

≤0.1% RH per °C

Response Time (to 90% change at 20°C)

110 sec

Annual Drift ≤1%

Output Scaling

0-100% RH

Temperature:

Active Output Accuracy ±0.5°C

Active Output Temperature Scaling

10° to 35°C (50° to 95°F)

Self-Heating Error (Resistive temperature only)

≤±0.5°C at 20° to 30°C (68° to 86°F); ≤±0.75°C outside of 20° to 30°C (68° to 86°F)

Operating Environment:

Operating Temperature

0° to 50°C (32° to 122°F)

Operating Humidity

0-100% RH noncondensing (Unit will recover from saturation)

Housing:

Material

ABS plastic with UL V-0 5VB Flame Class

Mounting Holes

US and European junction box

EMC Conformance: EN61000-6-3:2007+A1:2011 Class B; EN61326-1:2006 Class B; EN61000-6-1:2007

HEW SERIES

Ideal

for Bid

Spec!

HQ0001720.C 01131

Advertising