Veris Industries H970LCA Install User Manual

H970lca, 970lca, Notice

Advertising
background image

CURRENT MONITORING

Z203252-0E

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

10101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

INSTALLATION GUIDE

TM

Split-Core Low Current 4-20mA & 0-5VDC

DC Current Transducer

Installer’s Specifications

Technology

Open loop Hall effect

Amperage Range

0 to 20/40/80 ADC (slide switch selectable)

Sensor Supply Voltage

15-30VAC/DC for 4-20mA output;

12-30VAC/DC for 0-5VDC output

Supply Current

35mA max.

Isolation

600VAC rms

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Output

4-20mA and/or 0-5VDC

Accuracy

±3% F.S. combined linearity, hysteresis, and repeatability

The product design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

Wiring ExamplE

H970LCA

TM

970LCA

DimEnsions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

quick install

Disconnect and lock out power to the conductor to be monitored.

1.

Choose a location for the sensor. The monitored conductor must pass through the

2.

iris, and the sensor must be at least 1/2” from any uninsulated conductors.

Install the adjustable mounting bracket to the back of the enclosure using the

3.

included screws.

Connect supply voltage wires to the terminals marked Power (+) and Gnd (-).

4.

Wire the output (mA or VDC) connections between the sensor and the controller.

5.

Snap the sensor over the conductor to be monitored and clip the assembly to the

6.

mounting bracket.

Set the field-selectable switch to the desired amperage level (see page 2).

7.

Fan or Pump

CONTROLLER

4-20mA DC

Analog

Input

MOTOR

CONTACTOR

Removable Mounting Bracket

Self-gripping

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4”

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted
on either side for added
installation flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan-

dard DIN rail.