Veris Industries H663 SERIES Datasheet User Manual

Branch current monitor, split-core, Monitor current on every breaker, H663 series

Advertising
background image

p

o

wer/ener

g

y monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

FEATURES

Reports current consumed on each circuit in the panel board...one product covers

multiple points

Provides Modbus registers for current limit warnings and alarms...prevents

breaker trips

Integrates with available network display for local indication

Split-core design and network compatibility... ideal for retrofit applications

Up to 63 H663s can be networked on one Modbus RS-485 drop...simplified

wiring

Split-core CTs are perfect for quick installation on critical load applications that

can’t be powered down

DESCRIPTION

The H663 Series split-core branch circuit current monitoring system provides a cost-
effective solution for electrical load management. It is ideally suited for applications
where load capacity requirements are dynamic, such as data centers and sales floors.
The split-core housing makes this device perfect for retrofit projects.

The H663 monitors the current draw of each critical breaker in a panelboard. The
accumulated information can be transmitted to a Modbus host and/or viewed on
an optional local display via an RS-485 network. Data updates occur approximately
once per second to provide timely preventative maintenance information. As a circuit
approaches capacity, warning and alarm levels trigger (see graph, facing page).
Additional capacity can then be added, or loads balanced, to prevent costly downtime
from overloaded circuits and unexpected breaker trips.

APPLICATIONS

Retrofitting panelboards

Cost allocation

Protecting against overload

Managing and balancing loads

Lighting circuits

Monitor Current on Every

Breaker

Branch Current Monitor,

Split-Core

SPECIFICATIONS

Inputs:

Input Power

120 VAC (+10/-25%) line-to-neutral, 50/60 Hz; (208/230 VAC for H663SM-xxE)

Frequency

50/60 Hz

Accuracy:

Accuracy

±5% of reading from 5 A to 50 A

Sampling Frequency

1280 Hz

Update Rate

1.2 sec

Outputs:

Type

Modbus® RTU

Connection

DIP-switch selectable 2-wire or 4-wire

Address

DIP-switch selectable address 1 to 247

Baud Rate

DIP-switch selectable 2400, 4800, 9600, 19200

Parity

DIP-switch selectable NONE, ODD, EVEN

Communication Format

8 data-bits, 1 start-bit, 1 stop-bit

Mechanical:

Connection to Conductor

Inductive split-core CT *

Number of Channels

42, 30, 24, 12, or 1 (Choose one option)

Environmental:

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH, non-condensing)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

* Do not apply 300 V Class current transformers to circuits having a line-to-neutral voltage greater than 300 V, unless adequate additional insulation is applied

between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products

operated on circuits above their published ratings.

Year

Warranty

5

H663 SERIES

HQ0001911.A 01121

H663

H663 Series transducers are sold as an open device.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.