Veris Industries H308 Install User Manual

H308, Notice, Danger

Advertising
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Z204964-0C

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Micro Split-Core Current Switch,

Adjustable Trip Point

Installer’s Specifications

Amperage Range

0.75 to 50 A Continuous

Setpoint

Adjustable

Sensor Supply Voltage

Induced from monitored conductor

Insulation Class

600 VAC RMS (UL), 300 VAC RMS (CE), insulated conductors only

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Frequency

50/60 Hz

Status Output Ratings

N.O. 1.0 A@30 VAC/DC, not polarity sensitive

Off State Resistance

Open switch represents 1+ MΩ of resistance

Terminal Block AWG Range

16-22 AWG

Terminal Block Torque Range

7 in-lb

Agency Approvals

UL508, E150462

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2010,

Installation Category III or equivalent. The product design provides for functional insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

WIRING EXAMPLE

H308

TM

308

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the enclosure containing the

conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller (solid-state

contact).

4. Snap the sensor over the wire to be monitored and push the latch until it is

securely closed. Clip the assembly to the mounting bracket.

5. Calibrate the current switch (see Calibration section).

6. Secure enclosure and reconnect power.

POWER

SOURCE

POWER

SOURCE

BUILDING AUTOMATION

Insulated Conductor ONLY

CONTROLLER

UNIT VENT HEATER

DI

DI

Removable Mounting Bracket

0.3”

(8 mm)

6 AWG max.

1.6”

(40 mm)

1.5”

(38 mm)

0.6”

(15 mm)

1.8”

(46 mm)

Ø 0.18” (x2)

(5 mm)

Setpoint

adjustment

screw here

US Patent 7,193,428
(other patents pending)

RoHS

Compliant