Veris Industries PVE SERIES Install User Manual

Pg/pv/pge/pve, Gauge pressure sensors, Installation guide

Advertising
background image

VERIS INDUSTRIES

environmental SenSorS

inStallation GUiDe

ZL0064-0A

PAGE 1

©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]

11091

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Gauge Pressure Sensors

Installer’s Specifications

Electrical:

Supply Voltage

10-28 VDC

Output

Deluxe: 0-5/0-10 VDC (3-wire) or 4-20 mA (2-wire)

Economy: 1-5 VDC (3 wire) or 4-20 mA (2-wire)

Load Impedance

>100kΩ

Standard Connection

Cable gland 24” (600mm) length

Pressure Port

1/4”NPT Male

Performance at 25°C (77°F):

Accuracy *

Deluxe: ±0.25% BFSL **

Economy: ±0.50% BFSL **

Media Compatibility

Fluids & gases compatible with 316L stainless steel

Pressure Cycles

>100 million cycles

Over Pressure

2x F.S. without change in calibration

Burst Pressure

5x rated pressure or 20,000 PSI

Environmental:

Shock

100G, 11 msec, 1/2 sine

Vibration

Deluxe: 20G peak, 20 to 2400 Hz

Economy: 10G peak, 20 to 2000 Hz

EMI/RFI Protection

Deluxe: yes

Economy: no

Rating

Deluxe: IP-66

Economy: IP-65

Operating Temperature Range

-40° to 85°C (-40° to 185°F)

Compensated Temperature Range

0° to 55°C (32° to 130°F)

Total Error Band Over Temperature

<±1% of FS

Humidity

0-95% RH, non-condensing

* Accuracy includes nonlinearity and hysteresis.

** BFSL = Best fit straight line

PG/PV/PGE/PVE

PG/PV/PGE/PVE

/05*$&

t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT

t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 3FBEBOEVOEFSTUBOEUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOH
 UIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOJU

t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT

Product IdentIfIcatIon

quIck Install

Insert probe into area to be measured.

1.

Wire according to diagrams. See Wiring section.

2.

PGE/PVE

PG/PV

Range

03 = 0 to 15 psig
(Deluxe only)
04 = 0 to 25 psig
05 = 0 to 50 psig
06 = 0 to 75 psig
07 = 0 to 100 psig
08 = 0 to 250 psig
09 = 0 to 500 psig
10 = 0 to 1000 psig
11 = 0 to 5000 psig
12 = 0 to 10000 psig

PG

Wetted Material

Output

B = 1-5VDC (economy only)
M = 4-20mA
V = 0-10VDC (deluxe only)
J = 0-5VDC (deluxe only)

A

Range

03 = -14.7 to 15 psig
(Deluxe only)
04 = -14.7 to 25 psig
05 = -14.7 to 50 psig
06 = -14.7 to 75 psig
07 = -14.7 to 100 psig
08 = -14.7 to 250 psig
09 = -14.7 to 500 psig
10 = -14.7 to 1000 psig
11 = -14.7 to 5000 psig
12 = -14.7 to 10000 psig

PV

= 316L stainless steel

Output

A

Call factory for ranges not shown.

Type

Blank = Deluxe
E = Economy

Type

Blank = Deluxe
E = Economy

Wetted Material

B = 1-5VDC (economy only)
M = 4-20mA
V = 0-10VDC (deluxe only)
J = 0-5VDC (deluxe only)

= 316L stainless steel