Fractional HP Motor Status Sensor/

Command Relay

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

H540/548

TM

540/548

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

Installer’s Specifications

Sensor Power

Induced from the monitored conductor

Amperage Range

H540: 0.25 to 15 A; H548: 0.5 to 15 A

Frequency Range

50-60 Hz

Operating Temperature Range

-15°C to 50°C (5° to 122°F)

Operating Humidity Range

0-95% non-condensing

Wire to Relay Contacts

Use 12 AWG (3.3 mm

2

) or larger wire*

Terminal Block Torque

Relay control terminals: 3.5 in-lb (0.4 N-m)

All

other terminals: 12 in-lb (1.35 N-m)

Relay:

Switching Capacity at 120 VAC

1 HP

Relay Output

SPST F.S. N.O. or N.C.

Relay Coil

24 VAC/DC; 36 mA nom

Current Sensor:

Sensor Supply Voltage

Induced

Status Output Rating

N.O. 1.0 A at 30 VAC/DC

Trip Point

H540: Fixed (on/off status); H548: Adjustable (belt loss detection)

Agency Approvals

UL508, Installation Category III

* For current loads up to 10A, use 75°C rated wire insulation. For loads greater than 10A, use 90°C

rated wire insulation.

Specification Note: For CE compliance, insulate conductor according to IEC 61010‑1:2001.

The product design provides for basic insulation only.

Dimensions

2.13"

(55 mm)

1.16"

(30 mm)

4.25"

(108 mm)

1.53"

(39 mm)

C L

C L

C L

Wire

Opening

Wire

Opening

Wire

Opening

1.16"

(30 mm)

4.25"

(108 mm)

quick install

1. Disconnect power sources prior to installation.

2. Remove the sensor lid and wire the command relay connections and relay controls

to the base.

3. Set the relay contact jumper.

4. This device has four wiring options, detailed on page 2-3 of this installation guide.

Choose the option appropriate to the application and follow instructions.

operation

The H540 and H548 devices combine a switching relay, a current status sensor, and a
Hand-Off-Auto (HOA) switch into a single housing. The device is connected in series
between the power source and the motor device, and the relay and HOA switch
control the on/off functioning of the motor. The current switch trip point is fixed at
0.25 A on the H540 and adjustable from 0.5 to 15 A in the H548. The maximum load
is 15 A for both devices. The H540 and H548 require no additional power source for
operation.

VERIS INDUSTRIES

, INC.

P

ORTLAN

D, OREG

ON USA

TOLL FREE

USA 1.800.35

4.8556

TEL USA

1.503.598

.4564

FAX USA

1.503.5

98.4664

540

HAND

OFF

AUTO

CAUTION:

Consult

instructions

prior to i

nstallation

!

STATUS O

UTPUT: 1

A@30VAC

/DC

RELAY CO

IL: 24VAC

/DC; 16m

A nom.

RELAY OU

TPUT: 16

(8)A@250

VAC; 3/4

HP

RS

OC

SO

SP

SC

VERIS INDUSTRIES, INC.

P

ORTLAN

D, OREG

ON USA

TOLL FREE USA

1.800.354.8556

TEL USA

1.503.598.4564

FAX USA 1.503.5

98.4664

548

HAND

OFF

AUTO

CAUTION

: Consult in

structions

prior to ins

tallation

!

STATUS O

UTPUT: 1

A@30VAC

/DC

RELAY CO

IL: 24VAC

/DC; 16m

A nom.

RELAY OU

TPUT: 16

(8)A@250

VAC; 3/4

HP

RS

OC

SO

SP

SC

Advertising