Veris Industries H8830 Install User Manual

H8830, Notice, Danger

Advertising
background image

POWER MONITORING

ZL0069-0A

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

10102

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

H8830

Installer’s Specifications

Input Power

110 to 120 VAC

Processor

ARM

Firmware

Field-upgradeable

Inputs

Pulse (2x dry contact), Modbus RS-485

Modbus Input

2-wire RS-485 (9600 or 19200 baud)

LED

2x RF, 2x RS-485, 2x pulse, Alive, Alarm

Radio Frequency

900 MHz ISM band

Radio Output Power

1 mW (optional 150 mW, consult factory)

Radio Max Range

1500 ft. (457 m) per hop

dimensions

Wireless Modbus/Pulse Transceiver

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

Product identification

quick install

Set the Modbuss address and system switches.

1.

Connect the pulse and Modbus hookups.

2.

Attach the antenna.

3.

Connect power to the H8830.

4.

H8830

Ø 0.17”

(4.4mm)

5.6”

(143mm)

6.6”

(168mm)

6.1”

(154mm)

3.0”

(76mm)

4.3”

(110mm)

MODEL

DESCRIPTION

H8830

Wireless Modbus/Pulse Transceiver

Advertising