RELAYS

INSTALLATION GUIDE

20A SPST Enclosed Relay With HOA Switch

Installer’s Specifications

Operating Temperature

-40° to 60°C (-40° to 131°F)

Operating Humidity

10-90% RH, non-condensing

Expected Relay Life

Electrical (@ rated current) 100,000 cycles;

Mechanical

(unpowered) 10,000,000 cycles

Relay Status

LED ON=energized

Wire Specifications:

Lead Length

14”(356mm) min.

Gauge

UL1015; Coil: 18AWG; Contacts: 12AWG; HOA monitoring wires: 16AWG

Insulation Class

277VAC RMS

Agency Approvals

UL 508 enclosed device listing, pollution degree 2

V121

V121

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out all power sources before beginning the
installation.

1. Using the threaded nipple, connect the relay to the desired enclosure through a

knock out hole.

2. Secure with the conduit nut provided.

3. Connect coil wires:

• Choose the coil common lead (white with yellow stripe) and connect it to

the common (-) source termination point.

• Choose either the low voltage (10-30VAC/DC, white with blue stripe) or

high voltage (120VAC, white with black stripe) lead, depending on the
application requirements, and connect it to the (+) source termination
point.*

Note: When connecting the control side of this device (#18 wires) to power
line circuits, provide currenting limiting at 7 amps max.

4. Connect relay contacts:

• Choose the two solid orange wires (N.O. contact) and connect to the

switched load.

5. Secure the enclosure and reconnect power.

* Isolate or insulate all non-terminated wires according to local electrical code requirements, i.e.
wire nut.

2.0"

(52 mm)

2.5"

(64 mm)

3/4" NPT Nipple

2.3"

(59 mm)

4.0"

(103 mm)

3.8"

(97 mm)

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION

Failure to follow these instructions will result in death or serious injury.

DANGER