Veris Industries PW SERIES Datasheet User Manual

Wet media differential pressure transducer, Jumper-selectable port swap feature, Pw series

Advertising
background image

PRESSURE

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

APPLICATIONS

Monitoring and controlling pump differential pressure

Chiller/boiler differential pressure drop

CW/HW system differential pressure

FEATURES

The jumper-selectable output switch for normal (4-20mA) or reverse

(20-4mA) operation provides application flexibility

Rugged, die-cast enclosure provides NEMA 4 sealing

Jumper-selectable port swap feature eliminates costly replumbing when the

high and low ports are improperly plumbed...change the jumper position from

normal to swap – problem solved!

Switch-selectable pressure ranges...fewer models to order and stock

Pushbutton and remote zero adjustment...maintain accuracy and prevent

callbacks with automatic zero calibration

Jumper-controlled electronic surge dampening for high stability

Pushbutton zero calibration – no trim pots to adjust

SPECIFICATIONS

Input Power

12 to 30VDC/24VAC nominal

Maximum Current Draw

DC: 125mA; AC: 280mA

Output

3-wire transmitter; user selectable 4-20mA (clipped and capped)/0-5V/0-10V†

Accuracy @ 25°C*

Range A, B, C: ±1% F.S.; Range D: ±2% F.S.**

Surge Damping

Electronic; 5-second averaging

Test Mode

Overrides output to full-scale (20mA, 5V, 10V)

Pressure Ranges (Selectable):

0-50 psig

0-5/10/25/50 psid

0-100 psig

0-10/20/50/100 psid

0-250 psig

0-25/50/125/250 psid

0-3.5 barg

0.35/0.7/1.75/3.5 bard

0-7.0 barg

0.7/1.4/3.5/7.0 bard

0-17.0 barg

1.7/3.4/8.5/17.0 bard

Product Operating Environment

-10° to 55°C (14° to 130°F); 0 to 90% RH noncondensing

Long Term Stability

±0.25% per year

Zero Adjust

Pushbutton auto-zero and digital input (2-pos terminal block)

Status Indication

Dual-color LED: Green = Normal, Green Blinking = Low > High, Red = Overrange, Red Blinking = Overpressure

Housing Material

White powder-coated aluminum

Sensor:

Media Compatibility

Media compatible with 17-4 PH stainless steel

Proof Pressure

Max. 2x F.S. range

Burst Pressure

Max. 5x F.S. range

Temperature Compensated Range

0° to 50°C (32° to 122°F); TC Zero <±1.5% of product F.S. per sensor ; TC Span<±1.5% of product F.S. per sensor, (2 sensors per unit)

Media Temperature Limits

-20° to 85°C (-4° to 185°F); 0 to 90% RH non-condensing

Fittings

psig: 1/8" NPT female thread, 17-4 PH stainless; barg: 1/8” BSPT female thread, 17-4 PH stainless

†Minimum input voltage for 4-20mA operation: 250 loop (1-5V) = 12VDC; 500 loop (2-10V) = 15VDC; Minimum input voltage for volt operation: 0-5VDC output = 12VDC; 0-10VDC output = 15VDC.

*Accuracy combines linearity, hysteresis, and repeatability. **FS is defined as full span of selected range in bi-directional mode.

EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Jumper-Selectable

Port Swap Feature

Wet Media Differential

Pressure Transducer

DESCRIPTION

The PW Series wet/wet pressure transducers incorporate microprocessor profiled

sensors for exceptional accuracy and reliability. Easy to use and designed to provide

exceptional installation savings, the PW Series is ideal for measuring pressure across

pumps, filters, heat exchangers, compressors, and other non-corrosive wet media

applications.

Microprocessor provides digital signal conditioning

Noise rejection reduces fluctuating readings due to noise or turbulence

Surge damping prevents false alarms by averaging fast peaks

Year

Warranty

5

PW

0

Actual Pressure
Digitally Conditioned Output

TIME

F.S.

PRESSURE

Noise Rejection

Surge Damping

Output Clamping

PW SERIES

HQ0001831.B 01131

Advertising