Veris Industries H940 Install User Manual

Danger, Notice, Installation guide

Advertising
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Z201498-0B

PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

01132

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Switch, Fixed Trip Point,

with Command Relay

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Relay Coil Power

24VAC/DC

Amperage Range

1.5 to 200 A

Status Output Ratings

N.O. 1.0A@30VAC/DC, not polarity sensitive

Insulation Class

600VAC RMS

Trip Point

Fixed at 1.5 A

Frequency

50/60Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH, non-condensing

Off State Resistance

Open switch represents 1+ MΩ

On State Resistance

Closed switch represents <200 mΩ

Terminal Block Wire Size

24 to 14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Installation Category

Cat III, pollution degree 2

Do not use the LED status indicators as evidence of applied voltage.

The product design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

WIRING EXAMPLE

TM

940

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the enclosure

containing the conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through center window when it is installed and
that will keep the product at least ½” (13 mm) from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller and between

the sensor the the relay power source.

4. Snap the sensor over the wire to be monitored and clip the assembly to the

mounting bracket.

5. Secure the enclosure and reconnect power.

Fan or Pump

CONTROLLER

Motor

CONTACTOR

DI

(Status)

DO

(Relay

Coil)

CONTROL

POWER

Removable Mounting Bracket

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

Self-gripping Iris

2.8”

(70 mm)

Ø 0.3”

(8 mm)

1.4”*

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can

be mounted

on three sides

for added

installation

flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan-

dard DIN rail.