Veris Industries EP2 SERIES Datasheet User Manual

Electropneumatic transducers, Ep series, Pressure

Advertising
background image

PRESSURE

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

SPECIFICATIONS

Input Power

24VAC/DC nominal, 30VAC max.; 150mA max.

Control Input

4-20mA/0-5V/0-10VDC; jumper-selectable

Input Impedance

4-20mA, 250Ω; 0-5V/0-10VDC, 10 kΩ

Manual Override

Jumper-selectable mode, digital pushbutton adjust

Alarm Contact

100mA@30VAC/DC (Pressure loss, manual mode, jumper selectable)

Accuracy

1% FS; combined linearity, hysteresis, repeatability

Compensated Temperature Range

-4° to 65°C (25° to 140°F)

Temperature Coefficient

±0.05%/°C

Operating Environment

10-90% RH noncondensing

Air Capacity

523 in

3

/min @ 45 psi (8570 cm

3

/min @ 310.3 kPa); 333 in

3

/min @ 20 psi (5456 cm

3

/min @ 137.9 kPa)

Supply Pressure

45 psig max.

Control Range

0-20 psig or 3-15 psig, jumper-selectable

Pressure Differential

0.1 psig (supply to branch)

Pressure Indication

Electronic, 3-1/2 digit LCD

Minimum Tubing Length

15 feet*

Port Connection

1/8” i.d. poly tubing

Media Connection

Clean, dry air, or inert gas. Do not use with oxygen service

*For shorter tubing runs use AA45 Pneumatic Capacitor

EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power

adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Electropneumatic Transducers

Year

Warranty

5

DESCRIPTION

The EP2 Series electropneumatic pressure transducer uses micro-controlled poppet

valve technology for highly accurate pressure sensing in multiple applications. The

poppet valves consume no air, eliminating unnecessary air losses in the system and

allowing for stable and reliable operation. The EP2 is comes installed on standard

SnapTrack, and an optional dust cover is available to protect from the environment.

An LCD display and LED indicators make it easy to read system status at a glance.

APPLICATIONS

Hospitals

Schools

Pneumatic dampers/actuators

FEATURES

Field-selectable 4-20mA/0-5V/0-10VDC input for application flexibility

Poppet valve technology for quiet operation

Manual override with set and hold feature...great for commissioning

those leaky systems

Multi-point calibration; 3-15 psi (5 point calibration) and 0-20 psi

(6 point calibration)

Pressure loss alarm provides a contact closure if the EP2 is unable to

achieve the desired output within a fixed length of time

Failsafe vent solenoids bleed branch pressure on power failure for added safety

Optional transparent plastic dust cover (AA43) protects units from dust

and tampering (required for CE)

Micro-Controlled With High-

Performance, Low-Power Coil

Poppet Valve Technology

EP Series transducers are sold as an open device.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.