Veris Industries TWS SERIES Install User Manual

Tws series, Notice, Lcd wall mount with analog setpoints

Advertising
background image

VERIS INDUSTRIES

environmental SenSorS

inStallation GUiDe

Z204455-0D

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

06101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

LCD Wall Mount with Analog Setpoints

Installer’s Specifications

Power Supply*

15 to 30VDC/24VAC, 100mA max.

Outputs,Analog

Switch Selectable 4-20mA or 0-10V/0-5VDC (switch affects both outputs)

Stability

±1% @ 20°C (68°F) annually, for two years

Temperature Coefficient

± 0.1%RH/°C above or below 25°C (typical)

Operating Temperature Range

10° to 35°C (50° to 95°F)

Temperature Accuracy

±0.5°C (±0.9°F)

Scaling

10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F) menu selectable

Calibration Offset

Adjustable ±9.9° in 0.1° increments

Setpoint Range

Minimum to Full Scale in 1° increments

* One side of transformer secondary is connected to signal common, so an isolation transformer or

dedicated power supply may be required.

To maintain CE compliance the connected power supply must have a CE mark supporting LV + CE

directives.

RTD/Thermistors in wall packages are not compensated for internal heating of product.

TWS SerieS

TWS SerieS

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

ProDuct iDentification

Setpoint

= Analog

TWS

Cal Certificate

0 = None
1 = 1 point Cal Validation
2 = 2 point Cal Validation

Option

Blank = None
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k w/11k w/Shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
Q = 1uA/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A 221, Thermistor
T = 100k, Thermistor

S

A

1.2"

(29 mm)

3.5"

(89 mm)

4.75"

(121 mm)

-

+

Enter

quick install

Select a mounting location away from ventilation sources. The sensor should be

1.

mounted on a vertical wall, about 4 1/2 feet above the floor.

Affix the backplate to the wall.

2.

Wire the device. Refer to wiring diagram.

3.

Install Cover.

4.