EnvironmEntal SEnSorS

inStallation GUiDE

Digital Pressure Transducer

Dry Media

Installer’s Specifications

Media Compatibility

Dry air or inert gas

Input Power

12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max.

Output

Field-selectable: 2-wire, loop-powered 4-20mA

(DC

only, clipped and capped), or 3-wire 0-5V/0-10V*

Pressure Ranges:

PX: 01

Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable

Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selectable

Unidirectional:

25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch selectable

Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable

PX: 02

Unidirectional: 1.0/2.5/5.0/10” W.C. F.S., switch selectable

Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S., switch selectable

Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selectable

Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, F.S., switch selectable

PXU: 05

Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable

Bidirectional:

±0.1/0.25/0.5/1.0/2.5/5/10” W.C. F.S., switch selectable

Unidirectional:

25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable

Bidirectional: ±25Pa/50Pa/100Pa/250Pa/0.5kPa/1kPa/2.5kPa F.S., switch selectable

Response Time

Standard: T95 in 20 sec, Fast: T95 in 2 sec, jumper selectable

Mode

Unidirectional or bidirectional, jumper selectable

Display (option)

Signed 3-1/2 digit LCD, indicates pressure, overrange indicator

Proof Pressure

3 psid (20.6kPa)

Burst Pressure

5 psid (34.5kPa)

Accuracy

±1% F.S. of selected range (combined linearity and hysteresis)

Temperature Effect

1” (250Pa) models: 0.05%/°C; 10” (2.5kPa) models: 0.01%/°C

(Relative to 25°C) 0° to 50°C (32° to 122°F)

Zero Drift (1-year)

1” (250Pa) models: 2.0% max.; 10” (2.5kPa) models: 0.5% max.

Zero Adjust

Pushbutton auto-zero and digital input (2-pos terminal block)

Operating Environment

0°- 60°C (32° to 140°F); 0 to 90% RH non-condensing

Fittings

Brass barb; 0.24” (6.1mm) o.d.

Physical

UL 94 V-O Fire Retardant ABS

EMC Conformance: EN 61000-6-3:2007 and A1:2011 Class B, EN 61000-6-1:2007

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor

with proper surge protection (EN 61000-6-1:2007 specification requirements).

* Minimum input voltage for 4-20 mA operation: 250 Ω loop = 13 VDC; 500 Ω loop = 19 VDC

PX SerieS

PX SerieS

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

ProDuct iDentification

quick install

1. Plan the installation. Panel or duct mount?

2. For duct mounting, thread the probe into the rear of the device housing.

3. Configure the internal tubing for the selected installation method.

4. Mount the housing vertically.

5. Attach pilot tubing.

Enclosure

D = Duct
P = Panel

Local Display

L = LCD Display
X = No Display

NIST

N = NIST
X = None

Response

S = Selectable
F = Selectable

Range

01 = 0-1"W.C./0-250Pa
02 = 0-10"W.C./0-2.500kPa

PX

Local Display

L = LCD Display
X = No Display

NIST

N = NIST
X = None

Response

= Selectable

Range

= 0-10”/0-2.500kPa

PXU

05

S

Z103591-0A

Differential Pressure

Transmitter

Inch H2O

4.5"

(114 mm)

8.0"

(202 mm)

2.2"

(55 mm)

3.3"

(84 mm)

Advertising