Spot Leak Detectors

Spot Leak Detectors

DESCRIPTION

SD, SD-R01, SD-Z and MX1 Spot Detectors detect conductive fluids at a single point

for the most economical way to detect fluids in small, confined areas. These devices

are commonly used in small rooms and in air-conditioning drip pans. Use only with

SC conductive fluid leak detection cables.

Veris offers four models of spot detectors which can integrate with various building

management systems.

FEATURES

Simple installation – screw, or ram-set to floor (SD, SD-R01, SD-Z)

Simple operation – no maintenance

Solid-state design...no moving parts to fail

SD, SD-R01, SD-Z models have polymer-coated sensing probes...no exposed

metal that will rust

All models are fully potted for water-proofing...maximum durability

SPECIFICATIONS (SD, SD-R01, SD-Z)

Input Power (SD-R01 Only)

24VAC/VDC ± 10%; 0.1A max.

Outputs:

Solid-state (SD Only)

[email protected] min., 0.1A max.; [email protected] min., 0.1A max.

Relay (SD-R01 Only)

Dry Contact, Form C; 1 A@24VDC, 0.5A resistive@120VAC

Leader Cable (NSC):

Length

SD: 14 ft. (4.2 m); SD-R01: 14 ft. (4.2 m); SD-Z: 10 ft. (0.3 m) (2 cables included)

Connector (SD-Z Only):

1 male, 1 female; 4 pin, 0.96” (24.38 mm) diameter; connects to SC or NSC Cable

Operating Environment:

Temperature

0° to 50°C (32° to 122°F)

Humidity

5% to 95% RH non-condensing

Altitude

10,000 ft. (3,048 m) max.

Storage Environment

-20° to 70°C (-4°to158°F)

SD

SD-Z

MX1

SPECIFICATIONS (MX1)

Input Power

12-30VDC/24VAC; 10-year lithium battery model available

Max Current Draw, Voltage Units Only 10mA

Output

N.C. solid-state, (opens on alarm)

Output Rating

30VAC/[email protected] max., not polarity sensitive

Sensing Electrodes

Gold plated

Operating Environment:

Temperature

-20° to 80°C (-4° to 176°F)

Humidity

0 to 100% RH

MODEL

DESCRIPTION

SD Spot Detector

n

Operates on either 12-36VAC or 18-36VDC power

n

Includes a 14 ft (4.2 m) leader cable

SD-R01 Spot
Detector with
Relay Output

n

Works with any system that accepts dry contacts

n

Operates on 24VAC/VDC±10%

n

Automatically resets when conductive fluid is no longer present

(AC power only; if DC power is used, device must be reset by

disconnecting power momentarily)

n

Includes a 14 ft (4.2 m) leader cable

SD-Z Spot
Detector

n

Designed for use with the all detection panels, with SC sensing

cable to integrate both zone and spot detection into one panel

n

Powered by the LD300, LD1000, LD5100, LDRA6, or LD2000

n

When used with a distance read panel (LD2000 or OD5200), the

location of the leak will be identified (simulates 50 feet)

n

Includes one male and one female end connector, each on a 1 ft

(30 cm) lead wire

MX1 Spot
Detector

n

Battery-operated or 12-30VDC/24VAC powered

SD, SD-R01, SD-Z & MX1

HQ0001797.B 01131