POWER MONITORING

INSTALLATION GUIDE

E30

SPECIFICATIONS

Inputs:

Input Power

90-277VAC, 50/60 Hz

Accuracy:

Power/Energy

IEC 62053-21 Class 1, ANSI C12.1-2008

Voltage

±0.5% of reading 90-277V line-to-neutral

Operation:

Sampling Frequency

2560 Hz

Update Rate

1.8 seconds (both panels)

Outputs:

Type

Modbus RTU

Connection

DIP switch-selectable 2-wire or 4-wire, RS-485

Address

DIP switch-selectable address 1 to 247 (in pairs of 2)*

Baud Rate

DIP switch-selectable 9600, 19200, 38400

Parity

DIP switch-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

Termination

5-position depluggable connector

(TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Terminal Block Torque

4.4 to 5.3 in-lb (0.5 to 0.6 N-m)

Mechanical:

Ribbon Cable Support

4 ft. (0.9 m) flat ribbon cable ships standard;

up

to 20 ft. (6 m) available

Environmental:

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH noncondensing)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Altitude of Operation

3000 m

Agency Approvals

UL508, EN61010

* See Configuration section for details.

Panelboard Monitoring System

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

TABLE OF CONTENTS

Product Identification

2

Quick Install

2

Operation

2

Dimensions

2

Product Diagram

3

Data Output

3

Blink Codes for Status LED

3

Solid-Core Current Sensor Accuracy

3

Installation

4

Wiring

7

Configuration

8

Default DIP Switch Settings

8

Address Setup

9

Commissioning

10

Recommended Accessories

10

Safety

10

Troubleshooting

11

China RoHS Compliance Information (EFUP Table)

11