Z205667-0E

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

Power MoNITorING

INSTALLATIoN GUIDe

E31

Installer’s Specifications

Inputs:

Input Power

90-277VAC, 50/60 Hz

Accuracy:

Power/Energy

IEC 62053-21 Class 1, ANSI C12.1-2008

Voltage

±0.5% of reading 90-277V line-to-neutral

Operation:

Sampling Frequency

2560 Hz

Update Rate

1.8 seconds (both panels)

Overload Capability

22 kAIC

Outputs:

Type

Modbus RTU

Connection

DIP switch-selectable 2-wire or 4-wire, RS-485

Address

DIP switch-selectable address 1 to 247 (in pairs of 2)*

Baud Rate

DIP switch-selectable 9600, 19200, 38400

Parity

DIP switch-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

Termination

5-position depluggable connector

(TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Mechanical:

Ribbon Cable Support

4 ft. (0.9 m) flat ribbon cable ships standard;

up

to 20 ft. (6 m) available

Environmental:

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH noncondensing)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Altitude of Operation

3000 m

Agency Approvals

UL508, EN61010

* See Configuration section for details.

Panelboard Monitoring System

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class B digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a residential environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area may cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

Product IdentIfIcatIon

E31

E31

Description

A = Advanced board
B = Intermediate board
C = Basic board

# of CTs

002 = 2 adapter boards, no CTs, no cables
004 = 4 adapter boards, no CTs, no cables
42 = 2 adapter boards, 42 50A CTs, 4 ft. round ribbon cables
84 = 4 adapter boards, 84 50A CTs, 4 ft. round ribbon cables

table of contents

Quick Install

2

Operation

2

Dimensions

2

Product Diagram

3

Data Output

3

Blink Codes for Status LED

4

Solid-Core CT Accuracy

4

Installation

4

Wiring

8

Configuration

9

Default DIP Switch Settings

9

Address Setup

10

Commissioning

11

Recommended Accessories

11

Safety

11

Troubleshooting

12

China RoHS Compliance Information IEFUP Table)

12