Veris Industries H280 SERIES Datasheet User Manual

Load status switch, Provides status for manually switched loads, H280 series

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

SPECIFICATIONS

Sensor Power

Line powered

Operating Temperature

-15° to 60°C (5° to 140°F)

Operating Humidity

10-90% RH noncondensing

LED Status

GREEN LED=status normal; RED LED=status alarm

Frequency

50/60 Hz

Wire Specifications:

Lead Length

14” (356 mm) min.

Gauge

UL1015; Neutral: 18 AWG; Line: 12 AWG; Status: 16 AWG

Agency Approvals

UL 508 open device listing

Do not use the LED status indicators as evidence of applied voltage.

DESCRIPTION

The H280 load status switch monitors both voltage and current on manually-

switched loads (e.g., lights/fans in bathrooms). This device provides status

monitoring for loads that are not, or cannot be, controlled by a control system.

The H280 also saves cost by eliminating the need to connect a digital output to

prove status.

APPLICATIONS

Lighting

Bathroom Fans

Sump Pumps

Traffic Lights

Roadside Lighted Areas (e.g., bus stations)

Parking Lots/Garages

FEATURES

Wide voltage range (110-277VAC)...easy to use in many applications

Low current threshold (100mA) offers great sensitivity for those small loads

Nipple mount housing can be connected to any 1/2” conduit knockout for

installation versatility

Dual-color LED for easy visual inspection...control system is not required

Isolated status output protects control system

Provides Status For

Manually Switched Loads

Load Status Switch

Year

Warranty

5

H280

H280 SERIES

TM

HQ0001773.B 01131

Advertising