DESCRIPTION

LD5200 distance read panel has an innovative touch screen interface that accesses

all basic functions. The LD5200 can operate as a stand-alone device, with the user

configuring, monitoring, locating, and acknowledging leaks at the panel. It can

also be connected to the building network and accessed via a web interface, which

expands the capabilities of the unit, adding a convenient interactive facility mapping

tool. When a leak is detected, the mapping tool displays the exact location in the

building where the alarm occurred. Multiple communication protocols make the

LD5200 readily compatible with existing building systems. Use with our SC, SC-C, or

SC-H sensing cable for a complete solution to leak detection.

FEATURES

Touch screen interface allows access to basic functions...stand-alone

configuration and monitoring

Web interface offers expanded capabilities through the building mapping

tool...pinpoint leaks quickly and accurately

Multiple communication protocols available...easy integration into building

systems

Acts as a master device for up to 127 leak detection units with up to 1000 feet

of SC cable or 7000 feet of SC-C cable...monitor large areas with only one device

Detailed alarm history with time and date stamps...assists in troubleshooting

SPECIFICATIONS

Input Power

100-240VAC@500mA max., 50/60 Hz

Inputs:

Water Leak Detection Cable

Requires 15 ft. (4.5 m) leader cable kit (LC-KIT or LC-KIT-M)

Maximum Length

10000 ft. (3048 m)

Minimum Length

35 ft. (1037 m)

Detection Accuracy

± 2 ft (0.6 m) + 0.5% of the cable length

Detection Repeatability

± 2 ft (0.6 m) + 0.25% of the cable length

Detection Response Time

5-990 sec ± 2 sec, software adjustable in 5 sec increments

Outputs:

Analog

4-20mA Loop Powered, 18-36VDC, RL = 500 Ω max.

Relay

2 Form C Leak Relays, 2 Form C Cable Break Relays; 1A@24VDC, 0.5A resistive@120VAC;

configurable for supervised or non-supervised, latched or non-latched

Maintenance Relay

1A@24VDC, 0.5A resistive @120VAC; configurable for supervised or non-supervised, latched or non-latched

Communications Ports:

EIA-232

9600 baud, No parity, 8 data bits, 1 stop bit

EIA-485 (Port 1, Port 2, Port 3)

9600, 19200, or 38400 baud (selectable); No parity, 8 data bits, 1 stop bit

RJ-45

10/100 Bast T ethernet port (TCP/IP)

Protocols:

Terminal Emulation (EIA-232)

VT100 compatible

Modbus RTU (EIA-485)

Master and slave; RTU Mode; BACnet MS/TP; N2, slave

RJ-45

Ethernet, TCP/IP; Modbus/TCP/UDP, Master and slave; SNMP V1, V2, V3, NTP, SMTP, DNS, BACnet/IP

Alarm Notification:

Audible Alarm

85dBA@2 ft. (0.6 m); re-sound 0-999 min

Visible Alarm

Indicated on LCD touch screen and through web interface

Logging Capabilities:

Event Log

Last 1024 events, downloadable to .txt files

Trend Log

Cable current level every day for the last 365 days, downloadable to .txt files

Login Security :

LCD Touch Screen

No password required to view controller status and data. Administrator password limits access to configuration options.

Web Interface

Username and password can be configured

Front Panel Interface:

Display

480 x 272 pixel color backlit LCD touch screen; 95.04 mm x 53-85 mm

Operating Environment:

Temperature

0° to 50°C (32° to 122°F)

Humidity

5% to 95% RH non-condensing

Altitude

15000 ft. (4572 m) max.

Mounting

Type 1 wall mount enclosure

Agency Approvals

CE; ETL listed: conforms to UL 61010-1, EN 61010-1; CAN/CSA C22.2 No. 61010-1; RoHS compliant