Veris Industries H8932 Datasheet User Manual

Network display, Modbus bridgepoint, Net w ork inte gra tion

Advertising
background image

net

w

ork inte

gra

tion

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

DESCRIPTION

The H8932/H8936 serves as a display for Modbus data. The product sits in series

between downstream metering devices and the upstream master, providing a

display of the data passing through it. Each register of the H704, H663, H8238,

H8035, H8036, E50Cx, and E51Cx energy monitors is viewed. The E30 and E31

meters are also supported, but the H8932/H8936 only presents a subset of the most

important data points measured. The H8936 is enclosed in a box for easy installation,

while the H8932 is available with no box for fast mounting to a panel.

APPLICATIONS

Allocating load-based costs

Managing loads

Overload protection

Collecting energy data

Tenant submetering

FEATURES

Large 1” x 4” backlit LCD with adjustable brightness control for easy viewing

Multi-color LED shows alarm status at a glance

Pass-through communications to other Modbus® devices*

Easy keypad setup

Monitor a variety of Veris power transducers from a single location

*Ot

her Modbus devices must respond to the “Report Slave ID” command (11h) to allow

pass-through communications from upstream network.

Modbus Bridgepoint

Network Display

SPECIFICATIONS

AC Power Source

Dedicated 120VAC, line-to-neutral; fused

Fuse Ratings

200mA@250 5x20 mm Fast-Blo

AC Power Voltage Tolerance

(90-132VAC) for 120V

AC Power Frequency

50/60 Hz

AC Power Termination

2-position Euro-style pluggable connector (max. wire size 12 gauge)

Terminal Block Torque

4.9 in-lb (0.56 N-m)

Alternate DC Power Source

12VDC, 300mA unfused (auxiliary input disabled if line connected)

Operating Temperature Range

0° to 50°C (32° to 122°F); <95% RH noncondensing

Storage Temperature Range

-20° to 70°C (-4° to 158°F)

Network Communications:

Interface

Downstream: RS-485; Upstream: RS-485, RS-232

Protocol

Modbus RTU

Baud Rate

UI-selectable 2400, 4800, 9600, 19200

Parity

UI-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

RS-485

¼ load transceivers; duplex is UI-selectable 2-wire or 4-wire; 5-position Euro-style pluggable connector

RS-232 (Upstream only)

DCE, no handshaking; DB-9 connection; pin 2: transmitted data from display; pin 3: received data to display; pin 5: ground

Terminal Block Torque

4.4 in-lb (0.5 N-m)

UI-Switch Inputs:

Number/Function

Four (METER, UP, DOWN, SELECT)

Auxiliary Input (Remote Alarm):

Type

Contact closure or pull-to-ground (10 mA max.)

Isolation

Optical to 2500VAC

Sense

UI-selectable N.O. or N.C. (i.e. Closed = Alarm or Open = Alarm)

Terminal Block Torque

3.5 to 4.4 in-lb (0.4 to 0.5 N-m)

LCD:

Size

1” x 4” visible area, 2 lines x 16 characters per line

Backlight

Green, UI-adjustable brightness in 10 steps

Status (Tri-Color LED)

Green = normal operation; Yellow = warning; Red = alarm

H8936

H8932

H8936 & H8932

HQ0001809.C 01131

Advertising