Veris Industries MX1 SERIES Install User Manual

Mx1 series, Moisture detector, Installation guide

Advertising
background image

Z202169-0K

PAGE 1

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

06083

6%2)3

environmental SenSorS

inStallation GUiDe

Moisture Detector

quick install

Installer's Specifications

MX1 SerieS

MX1 SerieS

Dimensions

/05*$&

t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT

t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 3FBEBOEVOEFSTUBOEUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOH
 UIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOJU

t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT

ProDuct iDentification

Input Power

12-30VDC/24VAC; 10-year lithium battery model available

Max. Current Draw, Voltage Units Only

10mA

Output

N.C. solid-state; opens on alarm

Output Rating

30VAC/DC @ 0.1A max., polarity insensitive

Sensing Electrodes

Gold plated

Sensor Power, Voltage Units Only

24VDC/24VAC nom., 30VDC/30VAC max.

Operating Environment:

Temperature

-20° to 80°C (-4° to 176°F)

Humidity

0 to 100% RH

Power Source

MX1

B = Battery
V = 12-30VDC/24VAC

0.3"

(7 mm)

0.3"

(7 mm)

0.6"

(14 mm)

0.75"

(19 mm)

1.75"

(44 mm)

1.2"

(30 mm)

0.5"

(13 mm)

Wiring

POWER SOURCE

DIGITAL CONTROL

Digital Input

Black

Red

NOTE: Power supply not required

for battery powered version

White

Green

12 to 30VDC/24VAC

Install the MX1 in the area to be monitored (e.g. under carpet, on pipe, in

1.

condensate pan, etc.). Install bottom side down, so that probes will be in contact
with any moisture that collects.

Mount MX1 using self-tapping screw provided.

2.

Wire as shown.

3.

Equivalent Resistance Values of Water

Water

Resistance

Distilled

2000 kΩ

Filtered

350 kΩ

Tap

300 kΩ

Ice (Melted)

150 kΩ

Detergent

100 kΩ

Salt

75 kΩ

oPeration

Top

Bottom

When the area surrounding the device is dry, there is infinite resistance between
the probes. When liquid comes into contact, the resistance decreases. When the
resistance is <1000 kΩ, the alarm will trigger.

The following table shows typical resistance values for several common solutions.
These values are approximations; the resistance will vary greatly with concentration
of contaminants in the water.

All sensors are factory tested in clean, filtered water at 27VAC. Do not use the MX1
sensor in distilled water.