CURRENT MONITORING

INSTALLATION GUIDE

Z201760-0E

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

01121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Switch, Adjustable Trip Point

Installer’s Specifications

Amperage Range

1.25-50 A Continuous

External Supply Voltage

5-30 VDC

Insulation Class

600 VAC RMS (UL) 300 VAC RMS (CE)

Frequency

50/60 Hz

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Hysteresis

10% typical

Status Output Ratings

N.C. 0.1 A@5-30 VDC polarity sensitive

Off State Resistance (max.)

34 µA@5 VDC; 200 µA@30 VDC

On State Voltage Drop

1.9 VDC (max.)@0.1 A

Terminal Block Max. Wire Size

14 AWG

Terminal Block Torque (nom.)

4 in-lbs (0.45 N-m)

Agency Approvals

UL508, E150462

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2010,

Installation Category III or equivalent.

The unit design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

WIRING EXAMPLE

H606

TM

606

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the enclosure containing the

conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller (solid-state

contact) or external power supply.

4. Snap the sensor over the wire to be monitored and clip the assembly to the

mounting bracket.

5. Calibrate the sensor (see page 2) with the load running normally.

6. Secure enclosure and reconnect power.

Motor

Fan or Pump

DDC CONTROLLER

Insulated Conductor ONLY

DI

-

+

CONTACTOR

-

5-30VDC

POWER SOURCE

+

-

+

2.5" *

(64 mm)

2.1"

(54 mm)

3.5"

(89 mm)

2.9"

(74 mm)

0.4” x 0.2”

(10 mm x 5 mm)

Slot (2x)

1.2"

(31 mm)

Removable Mounting Bracket

0.7"

(18 mm)

0.5"

(13 mm)

2.1"

(54 mm)

1.0" *

(26 mm)

0.6"

(16 mm)