DESCRIPTION

Hawkeye 904, 934, and 720 current monitoring devices provide unique solutions

for accurately monitoring status of motors controlled by variable frequency drives.

The microprocessor-based H904 and H934 store the sensed amperage values

for normal operation at various frequency ranges in non-volatile memory. This

information allows the device to distinguish between a reduced amp draw due to

normal changes in the frequency and an abnormal amp drop due to belt loss or other

mechanical failures. The relay on the H934 is isolated from the current switch, and all

relay connections are externally accessible on the device.

The H720 analog output corresponds to current in the monitored conductor from 10

to 80 Hz.

APPLICATIONS

Monitoring positive status on motors controlled by variable frequency drives

Replacing pressure switches

Measuring current and load trending

FEATURES (H720)

Analog output

Superior to Hall effect and metal core sensors...frequency tolerant 10-80 Hz

Accurate to 0.5% of full scale

Suitable for load side monitoring of VFDs

Adjustable zero and span for precise scaling

Adjustable mounting bracket for easy placement

FEATURES (H904 and H934)

Microprocessor-based...real labor saver...No need to calibrate to

detect belt loss on VFDs

Self-adjusting trip point...factory programmed to detect belt loss

undercurrent conditions

Provides accurate status for VFD loads...prevents costly long-term failures

Automatically compensates for the effects of frequency and amperage

changes associated with VFDs

Nuisance Reduction feature...provides a secondary setpoint option of

50% of the originally measured current

LED indicates normal and alarm conditions...rapid troubleshooting

Huge labor savings...no need to calibrate in live starter enclosures...

install and go

Available with a relay (H934)...status and control in one package,

saving time and space

Bracket can be installed in three different configurations...added flexibility

Monitors both frequency and amperage...distinguishes normal drops in

amperage due to frequency changes from abnormal drops due to

mechanical failure

Split-core design is ideal for retrofits...no need to remove conductor

5-year warranty

Variable Frequency Drive

Monitoring and Control

VFD Switches and

Current Sensors

SPECIFICATIONS

Sensor Power

H904/H934: Induced from monitored conductor; H720: 12-30VDC

Insulation Class

600VAC RMS

Frequency Range

H720: 10 to 80 Hz; H904/H934: 20 to 34 Hz for on/off status, 34 to 75 Hz for belt loss indication

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Off Delay (H904/H934)

0 sec to 2 min.

Accuracy (H720)

0.5% (combined linearity, hysteresis, and repeatability)

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing

Do not use the LED status indicators as evidence of applied voltage.

U.S. Patent No. 5,705,989

H904

H934

H720

Year

Warranty

5

H904 , H934 & H720

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

Maximize Reliability

Minimize Installed Cost

HQ0001758.B 01131