Veris Industries CWV SERIES Datasheet User Manual

Wall co2 sensors, dual analog outputs, Cwv series, Air qu alit y

Advertising
background image

AIR QU

ALIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Wall CO2 Sensors,

Dual Analog Outputs

Dual Analog Outputs, Switchable

0-3/5/10 Volt/4-20 mA Output

DESCRIPTION

The CWV Series is a non-dispersive infrared sensor designed for measuring CO2

concentration in office and living spaces. Its 2000 ppm measurement range makes it

an ideal solution for meeting ASHRAE and other ventilation control standards.

The CWV Series features multiple output options, microprocessor-based digital

technology, and a unique self-calibration algorithm which improves long-term

stability and accuracy.

APPLICATIONS

Controlling HVAC in response to occupancy – save energy by providing

ventilation only as required

Improving tenant comfort

Schools, museums, airports, commercial buildings, etc.

OEM applications

Home automation

Big-box retail

Restaurants

C-Stores

Bid/Spec market

SPECIFICATIONS

Input Voltage

20 to 30VDC, 24VAC

Analog Output #1

4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)

Analog Output #2

4-20mA (clipped & capped) or 0-3VDC/0-5VDC/0-10VDC (jumper selectable)

Sensor Current Draw

200mA Maximum

Operating Humidity Range

0-95% RH noncondensing

Operating Temperature Range

0° to 50°C (32° to 122°F)

Housing Material

High impact ABS plastic

CO2 Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Measurement Range

0-2000 ppm

Accuracy

±40 ppm ±5.5% of measured value

Repeatability

±30 ppm ±4.5% of measured value

Response Time

<60 seconds for 90% step change

Relay Contacts

1A@30VDC, resistive; 30W max.

EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Year

Warranty

1

CWV

FEATURES

Microprocessor-based design reduces long-term drift and

calibration requirements

Non-dispersive infrared technology (NDIR) repeatable to ±30 ppm ± 4.5% of

measured value...high accuracy measurements

Innovative self-calibration algorithm...easy to maintain

5-year calibration interval (recommended)

Low ambient sensitivity

Improve comfort and facilitate compliance with ASHRAE 62.1 standard

for air quality

Demand control ventilation provides reduction in energy costs...helps with

green branding initiatives

Dual analog outputs...added user convenience

LED indication for power and error detection...reduces

time spent troubleshooting

Switchable 0-3/5/10V output...increased flexibility

US & European mounting holes...installation flexibility

Field calibratable...reduce costly downtime

4-20mA and voltage outputs in one unit...greater versatility

CWV SERIES

HQ0001742.B 01131

Advertising