Wireless Temperature and Humidity Sensors

SPECIFICATIONS

Inputs:

Input Voltage

Two 1.5 V AA lithium/iron disulfide batteries (3000 mAh min.)

Setup

Pushbutton setup

Outputs:

Wireless

802.11 B/G 2.4 GHz radio

Battery Indicator

Indicates low battery power (read by Gateway or JACE)

Temperature Output Range

Configurable in software: 0° to 50°C (32° to 122°F)

or 10° to 35°C (50° to 95°F)

Accuracy:

Temperature

±0.75°C (typical)

Humidity

±2% of full scale @ 25°C

Operating Environment:

Operating Temperature Range

0° to 50°C (32° to 122°F)

Operating Humidity Range

0 to 95% RH noncondensing

Storage Temperature Range

-40°C to 50°C (-40°F to 122°F)

Agency Approvals

EN61010-1; ETL; CE

HWXW SERIES AND TWXWXX

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

Accessories (sold separately)

Part Number

Description

AWB01

Wi-Fi configuration cable

AWB04

JACE Driver

3.5"

(89 mm)

4.8"

(121 mm)

1.2"

(30 mm)

PRODUCT OVERVIEW

The Aerospond HWXW Series and the TWXWXX wireless sensors monitor the
humidity and temperature, respectively, of the air inside a room. The HWXW series
has a temperature option to get both readings in one device. The sensors send
environmental readings over a standard building wireless (Wi-Fi) network. The
sensors can be integrated with the building controller using either a network wireless
gateway (Veris Aerospond NWGWA2), which converts data to either analog or digital
outputs, or with a JACE controller and driver (Veris AWB04) for direct integration.

QUICK INSTALL

1. Configure all devices in the wireless network using the Veris configuration

software, available at www.veris.com.

2. Affix the backplate on a vertical wall, about 4 ½ feet above the floor, away from

ventilation sources.

3. Insert two 1.5 V AA lithium/iron disulfide batteries (3000 mAh min.) into the

terminals on the back of the sensor.

4. Mount the sensor onto the backplate and attach the front cover.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

IMPORTANT NOTE: To comply with FCC & IC RF exposure requirements, the antenna used

for this transmitter must be installed to provide a separation distance of at least 20cm

from all persons and must not be co-located or operate in conjunction with any other

antenna or transmitter.

HW

Local Display

= No Display

Wireless

= Wireless

W

RH Option

1 = RH 1% NIST
2 = RH 2% NIST
H = RH 2%

Temp. Option

X = No temp.
T = Temp. transmitter

X

PRODUCT IDENTIFICATION

TW

Local Display

= No Display

Wireless

= Wireless

W

X

XX