DESCRIPTION

The durable PG/PV Series pressure transducers are ideal for a wide variety of HVAC/R

and industrial applications, such as refrigeration measurement, pneumatic pressure

measurement, gas pressure measurement, pump inlet, and outlet fluid pressure.

They are even compatible with extreme applications, such as aerospace and motor

sports equipment.

APPLICATIONS

Pump inlet/outlet and compressors

Hydraulic/pneumatic systems

Energy & water management

Refrigeration equipment, fluids

Gas pressure measurement

FEATURES

Rugged stainless steel construction (PG and PV)

Stainless steel wetted connector (PGE and PVE)

No silicon oil, no internal O-rings, no welds...fewer parts to fail

Sturdy construction...suitable for high shock and vibration applications

A wide operating temperature range of -40° to 85°C (-40° to 185°F)

for operation versatility

Rugged Stainless Steel Construction

Gauge Pressure Sensors

SPECIFICATIONS

Electrical:

Supply Voltage 10-28VDC

Output

Deluxe: 0-5/0-10VDC (3-wire) or 4-20mA (2-wire); Standard: 1-5VDC (3 wire) or 4-20mA (2-wire)

Load Impedance

>100 kΩ

Standard Connection

Cable gland 24” (600 mm) length

Pressure Port

1/4” NPT Male

Performance at 25°C (77°F):

Accuracy *

Deluxe: ±0.25% BFLS **; Standard: ±0.50% BFLS **

Media Compatibility

Fluids & gases compatible with 316L stainless steel

Pressure Cycles

>100 million cycles

Over Pressure

2x F.S. without change in calibration

Burst Pressure

5x rated pressure or 20,000 psi

Environmental:

Shock

100G, 11 msec, 1/2 sine

Vibration

Deluxe: 20G peak, 20 to 2400 Hz; Standard: 10G peak, 20 to 2000 Hz

EMI/RFI Protection

Deluxe: yes; Standard: no

Rating

Deluxe: IP-66; Standard: IP-65

Operating Temperature Range

-40° to 85°C (-40° to 185°F)

Compensated Temperature Range

0° to 55°C (32° to 130°F)

Total Error Band Over Temperature

<±1% of FS

Humidity

0-95% RH noncondensing

* Accuracy includes nonlinearity and hysteresis.

** BFSL = Best fit straight line

Year

Warranty

5

PGE/PVE

PG/PV

PG SERIES

HQ0001830.B 01131

Advertising