Current Sensors: 4-20mA

Analog Output

Load Trending With 4-20mA Output

DESCRIPTION

The Hawkeye 721LC, 721HC, and 921 provide accurate load trending information

with a proportional 4-20mA output signal. Preset slide-switches provide easy field

setup of sensed amperage range with no need for jumpers.

APPLICATIONS

Load trending

Motor control

Fan/Pump Status

FEATURES

Power the sensor, and receive the signal with only two wires...lower cabling

and commissioning costs than with traditional 3-wire sensors

Self-gripping split-core for fast retrofit installation...no need to remove

conductor (H921)

Economical solid-core features adjustable bracket for easy alignment (H721)

Factory calibrated switch-selectable ranges for high resolution and

installation ease

Three field-selectable ranges per unit...fewer versions to choose from, stock,

and install

Removable mounting bracket for installation flexibility

Bracket on H921 can be installed in three different configurations...

added flexibility

100% solid state, no moving parts to fail

5-year warranty

EXAMPLE LINEAR OUTPUT

Scale software as shown

SENSED AMPS

Selected Range*

4mA

0A

20mA

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

SPECIFICATIONS

Sensor Power

30mA (max)@12-30VDC

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Accuracy

±2% F.S. from 10% to 100% of selected range, but not less than ±0.4A

Response Time

2 sec.

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation

For applications requiring double or reinforced insulation, please contact the factory.