Maximize System Efficiency and

Gain Precise Power Quality with

1% Energy and Power Accuracy

Power Meter for Voltage-Mode CTs

DESCRIPTION

The H84xxV, H84xxVB, and H84xxVBS Series digital power meters deliver high

accuracy and high value at a competitive price.

Whether you are looking for a 1-phase pulse output meter to monitor kWh, or a

3-phase communicating meter to monitor THD, the H84xxV Series has the right

meter for you, in panel and wall mounting styles for your convenience.

The pulse output unit offers two pulse outputs. While kWh is standard, the second

pulse output provides a field-selectable choice between phase loss or kVARh.

The Modbus communications unit offers a choice between two data outputs, Full

Data Set (FDS) or Extended Data Set (EDS). Data points are listed on the next page.

APPLICATIONS

Energy management and performance contracting

Submetering for commercial tenants

Activity-based costing in commercial and industrial facilities

FEATURES

Revenue Grade measurements

Intuitive navigation with context-sensitive menus for easy use

Panel, wall, DIN rail mount...provide mounting flexibility

Digital power meters automatically detect and correct phase reversal,

eliminating the need to be concerned with CT load orientation...fast,

trouble-free installation

Real-time power monitoring via local display or through control/data

acquisition systems

Large, easy-to-read display

Multiple values displayed at the same time on an anti-glare display

featuring a green back-light

SPECIFICATIONS

Inputs:

Control Power

100 to 415 ± 10%VAC, 5VA, 45-60 Hz

DC

125 to 250VDC ± 20%VDC, 3W *

Voltage Input

UL: 600VAC; CE: 300VAC (L-N)

Current Input

CT Scaling

Primary: Adjustable from 5A to 32,767A

Measurement Input Range

1V RMS full scale (+20% over-range)

Accuracy:

Current and Voltage 0.5%

Power

ANSI C12.16, 1%

Measurement - True RMS

True RMS up to 15th harmonic, 3-phase AC System

Outputs:

Pulse Output #1

(kWH ) N.O. Static Output (240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation

Pulse Output #2 (H8463V/VB/VBS)

(Phase Loss or kVARh) N.C. Static Output(240VAC or 300VDC, 100mA max. @ 25˚C, derate 0.56mA per˚C above 25˚C) 2.41kV RMS isolation

Mechanical:

Weight

H84xxV: 0.8 lbs; H84xxVB: 6.35 lbs; H84xxVBS: 9.15 lbs

Protection Class

V: IP40 front, IP30 back; VB: NEMA 1, IP40

Environmental:

Operating Temperature Range

Meter: 0° to 60°C (32° to 140°F); Display: -10° to 50°C (14° to 122°F)

Storage Temperature Range

Meter and Display: -40°C to 85°C (-40° to 185°F)

Humidity Range

0-95% noncondensing

Agency Approvals

UL508; ANSI C22.2, Cat. III, Pollution Degree 2, for distribution systems up to 347VAC (L-N)/600VAC (L-L);

CE per IEC61010, Cat. III, Pollution Degree 2, for distribution systems up to 300VAC (L-N)/480VAC (L-L)

*For control voltages >415VAC to 600VAC order H84xxVBS

H84xx

H84xxVBS

Year

Warranty

5

H84xxV, H84xxVB, & H84xxVBS SERIES

BACnet

connec

tivity

via new

E8950

Gateway

HQ0001713.B 01131