Veris Industries G SERIES Install User Manual

G series, Notice, Carbon monoxide transmitter and fan controller

Advertising
background image

Z202025-0P

PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]

03131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Carbon Monoxide Transmitter

and Fan Controller

SPECIFICATIONS

Input Power

15-30VDC/24VAC, 0.3A@24VAC

Sensor Type

Digitally profiled Metal Oxide Semiconductor (MOS)

Sensor Life

5-10 years typical, replaceable

Detection Range

0 to 200 ppm

Analog Output

3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V (specify mA or V)

Output Scaling

User-selectable 100 ppm F.S. or 200 ppm F.S.

Response Time

2 min 30 sec sample interval cycle

Relay Output

N.O. Form A (SPST) 8A@30VAC/VDC; (Use with N.C. contactor)

Relay Setpoint

25 ppm

High Limit Setpoint

100 ppm for 30 minutes

High Limit Alarm Audible, 85 dB, resets below 100 ppm (solid-state contact for -AS version)

High Limit Contact (-AS Models)

250VAC/DC, 120mA max. Ron 35 Ω

LED Indicators

Solid Green = Normal; Solid Red = Call for ventilation;

Flashing

Green = Sensor life has expired; Flashing Red = High-limit alarm

Operating Temperature Range

-20° to 50°C (-4° to 122°F)

Operating Humidity Range

0 to 90% RH non-condensing

Coverage

5000 sq ft typical (465 sq m)

Housing

White powder coat over steel

G SerieS

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

PRODUCT IDENTIFICATION

INSTALLATION

1. Lock out all power supplies prior to installation.

2. Select a location for the sensor in a secure area where it will be accessible only

to qualified service personnel. Install the G Series sensor centrally in the parking
structure, near the main traffic paths, but away from outside air vents and
excessive drafts. Mount the unit securely to a wall or column at a height of about 5
ft. (1.52 m) from the floor.

3. Connect wiring as shown in the Wiring section. If using a voltage output model,

use the Output jumper to select 0-5 V or 0-10 V.

4. Apply power to the unit. A green LED on the circuit board indicates proper

operation of the power supply.

Coverage is not dependent on the sensor. Coverage is a function of the building structure and air
flow patterns. A minimum of one sensor for 5000 sq. ft. is recommended. Wide open areas where
the air is well mixed may require multiple sensors.

2.4"

(55 mm)

2.5"

(63 mm)

0.9" dia.

(22 mm)

4.5”

(114 mm)

4"

(102 mm)

5.0"

(127 mm)

2.25"

(57 mm)

G

D = Duct mount
W = Wall mount

Enclosure

Auxiliary Alarm Output

Output

A = Auxiliary Contact
X = None

= Standard

V = Field-selectable,
0-5/0-10VDC
M =4-20mA
R = Relay only

S

US or EU