Veris Industries G SERIES Datasheet User Manual

Carbon monoxide sensors, G series, Air qu alit y

Advertising
background image

AIR QU

ALIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Easy Control of Ventilation in

Parking Garages and Mechanical Areas

Carbon Monoxide Sensors

GW

GMxA

DESCRIPTION

G Series carbon monoxide sensors maximize energy savings, while ensuring optimal

ventilation in parking garages and other mechanical areas. The sensors allow

ventilation systems to be controlled by the amount of CO present in a location. The G

Series detects fluctuations in CO levels, and it signals air systems to provide an inlet

of fresh air optimal for the space at a given time. In this manner, the ventilation fan

does not need to run continuously, saving energy and reducing maintenance costs.

Upon alarm, the G Series will alert those in the area with both an audible and a

visual alarm.

The G Series devices are equipped with a relay contact that closes when CO level is

below 25 ppm and opens when the CO level is above 25 ppm. Sensor removal, power

interruption, or cut wires cause the external contactor (normally closed) to open and

start the fan. Minimum relay cycle time is 3 minutes to prevent fan short-cycling.
Audible Alarm: 85 dB alarm sounds if CO level rises above 100 ppm for 30 minutes.

APPLICATIONS

Controlling parking garage ventilation

Ensuring OSHA air quality compliance in commercial buildings and factories

Vehicle bays (ambulance/fire/taxi stations)

Mechanical rooms

Sally ports

SPECIFICATIONS (GMxA Monitor)

Input Power 24VAC/[email protected]

Inputs

Detect contact closure from sensor relay. Four channels. 24VDC loop

Output

Form C (SPDT) relay. 5A@30VAC

Alarm Indicators

Four, 10 mm red LED indicates alarm status

Power Indicator

Green LED indicates power supply operation

Operating Environment

-20° to 50°C (-4° to 122°F); 0 to 90% RH non-condensing

Physical

NEMA 1, metal enclosure, white

SPECIFICATIONS (G Series Sensor)

Input Power

12-30VDC/24VAC, 0.3A@12VDC, 0.3A@24VDC

Sensor

Digitally-profiled Metal Oxide Semiconductor (MOS)

Sensor Life

5-10 years typical, replaceable

Detection Range

0 to 200 ppm

Analog Output

3-wire sourcing 4-20mA or user-selectable 0-5V/0-10V (Specify mA or voltage)

Output Scaling

User-selectable 100 ppm F.S. or 200 ppm F.S.

Response Time

2 minutes 30 second sample interval cycle

Relay Output

N.O. Form A (SPST) 8A@30VAC/VDC (use with N.C. contactor)

Relay Setpoint

25 ppm

High Limit Setpoint

100 ppm for 30 minutes

High Limit Alarm

Audible, 85 dB, resets below 100 ppm; (Solid-state contact for -AS version)

High Limit Contact (-AS models)

250 VAC/DC, 120 mA max. Ron 35 Ω

LED Indicators

Normal=Green; Call for ventilation=Red; High-limit alarm=Flashing Red

Operating Environment

-20° to 50°C (-4° to 122°F); 0 to 90% RH non-condensing

Coverage

5000 sq. ft. typical (465 sq. m)

Physical

white powder coat over steel

FEATURES

Long-life replaceable sensor element

Microprocessor controlled...excellent stability

No calibration required...easy maintenance and worry-free operation

Metal oxide semiconductor (MOS) sensor

Interface to DDC system, GM panel, or direct fan control...easy integration with

existing systems

Onboard fail-safe 5 Amp alarm relay for direct ventilation fan control...simple

operation

Interface to control system via selectable 4-20mA or 0-5/0-10VDC output...

application flexibility

Audible exposure alarm 100 ppm, 30 minutes per UL 2034...easy

troubleshooting

G SERIES

HQ0001743.B 01131

Advertising