Veris Industries TWS SerieS Datasheet User Manual

Independent heat/cool or analog setpoint outputs, Tws series, Setp oint de vices

Advertising
background image

setp

oint de

vices

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Independent Heat/Cool Or

Analog Setpoint Outputs

Wall Mount Temperature

Transmitter with

Thermostat Functions

FEATURES

Independent heat/cool (TWS relay) or analog setpoint outputs (TWS analog)

provide application flexibility

LCD for local display of readings and setup values...easy visibility under any

lighting conditions

Offset function adjusts calibration offsets for temperature

Switch selectable 4-20mA or 0-5/0-10VDC analog outputs

Semiconductor temperature sensor can be field calibrated

DESCRIPTION

All TWS Series institutional grade temperature transmitters are field-programmable

and are designed to satisfy the demanding requirements of pharmaceutical labs,

hospitals, science labs, and other exacting applications. Internal jumpers control

access to a feature which allows field adjustment of calibration offsets. Tampering

can be prevented by setting a jumper to disable keypad program functions.

Analog Output

Analog output models feature a keypad to make adjusting temperature setpoint

values easy. They are unique in reporting the setpoint values back to a control system

by means of 4-20mA or 0-5/0-10VDC (output selected by slide-switch) signals.

Setpoint Relay

The TWS Series setpoint relay models measure temperature and offer thermostat

functionality. Two separate relays can be configured to control heat/cool in

thermostat mode.

APPLICATIONS

Hospitals and operating rooms, pharmaceutical labs

Clean rooms

Food processing plants

Environmental testing facilities, and other institutional applications

SPECIFICATIONS

Input Power

15-30VDC/24VAC, 100mA max.

Outputs, Analog

Switch-selectable 4-20mA (clipped and capped)/0-10V/0-5VDC (switch affects all outputs)

Outputs, Relay (Relay models only)

2 Form C (SPDT), 1A 30VDC, resistive, 30W max.

Temperature:

Accuracy

±0.5°C (±1°F)

Scaling

10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F), menu selectable

Calibration Offset

Adjustable ±10° in 0.1° (C or F) increments

Setpoint Range

Minimum to Full Scale in 1° (C or F) increments

Hysteresis (Deadband)

1° to 10°F in 1°F increments

Physical

UL 94-V-O fire retardant ABS

Year

Warranty

5

TWS

TWS SERIES

HQ0001873.B 01131