DESCRIPTION

CDL/CWL carbon dioxide sensors maximize energy savings, while ensuring optimal

ventilation. These sensors allow ventilation systems to be controlled by the amount

of CO2 present in a space. The CWL/CDL Series detect fluctuations in CO2 levels and

signal ventilation systems to provide an inlet of fresh air optimal for the space at a

given time saving energy and ensuring tenant comfort.

APPLICATIONS

Controlling ventilation in response to occupancy

Facilitating compliance with ASHRAE 62.1 standard for air quality

Office buildings, conference rooms, schools, retail stores, etc.

Individual or 3-in-1 CO2,

RH, and Temperature

Deluxe Duct and Wall

CO2 Sensors

SPECIFICATIONS

Input Power

20 to 30VDC/24VAC; 100mA max.

Analog Output

4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable)

Operating Temperature Range

CDL: 0° to 50°C (32° to 122°F)

CWL: No humidity option: 0° to 50°C (32° to 122°F); With humidity option: 10° to 35°C (50° to 95°F)

Operating Humidity Range

0 to 95% RH noncondensing

Housing Material

High impact ABS plastic

CO2 Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Output Range

0-2000/5000 ppm (programmable)

Accuracy

±30 ppm ±2% of measured value*

Repeatability

±20 ppm ±1% of measured value

Response Time

<60 seconds for 90% step change

RH Transmitter:

HS Sensor

Fully replaceable, digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138

Accuracy

±2% from 10 to 80% RH @ 25°C; NIST traceable multi-point calibration

Hysteresis

1.5% typical

Stability

±1% @ 20°C (68°F) annually for two years

Output Range

0-100% RH

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Temperature Transmitter:

Sensor Type

Solid-state, integrated circuit

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Output Range

10° to 35°C (50° to 95°F)

Relay Contacts:

1 Form C (SPDT) (on models without setpoint slider option)

1A@30VDC, resistive; 30W max.

RTD/Thermistors in wall packages are not compensated for internal heating of product.

EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Note: Rough handling and transportation may cause a temporary reduction of CO

2

sensor accuracy. With time, the ABC function will tune the readings back to the correct accuracy range. The default tuning speed is limited to

30 ppm per week.

FEATURES

Microprocessor-based design increases accuracy and reduces installation time

Non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of

measured value...high accuracy measurement

Innovative self-calibration algorithm...easy to maintain

5-year calibration interval (recommended)

Field-selectable outputs for operation flexibility

Integrated transducer and probe...eliminates the need to install a separate

pick-up tube

Snap-on faceplate...no screws required, making installation and service easy

Adjustable duct probe...simplifies installation and airflow monitoring

CO2, humidity, and temperature sensing all in one compact device...fewer units

to buy and install

C SERIES