Veris Industries EA20 SERIES Datasheet User Manual

Dc applications, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Direct Current Sensors:

Split-Core, mA

and Voltage Output

DC Applications

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

System Technology

H970: Open loop Hall effect; H971, EA20: Exclusive Pulse Reset Technology™

Amperage Range

H970: LC: 0-20/40/80; HC: 0-50/100/200 (slide switch selectable); H971: ±200ADC; EA20: 0-100ADC/0-150ADC/0-200ADC

Sensor Supply Voltage

H970: 15-30VAC/DC for 0-10VDC and 4-20mA outputs, 12-30VAC/DC for 0-5VDC output; H971, EA20: 12-24VDC*

Supply Current

35mA max.**

Insulation Class

H970: 840VDC; H971: 600VDC, EA20: 1000VDC

Temperature Range

H970: -15° to 60°C (5° to 140°F); H971, EA20: -30° to 60°C (-22° to 140°F)

Humidity Range

10-90% RH non-condensing

Output

H970: 4-20mA, 0-5VDC, 0-10VDC (2 options allowed per sensor); H971: Bidirectional 4-20mA (adjustable span)***; EA20: Unidirectional 4-20mA

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

H970 Accuracy:

Accuracy

±3% F.S. (combined linearity, hysteresis, and repeatability)

Repeatability

±1%

Linearity

±1%

H971/EA20 Accuracy:

Accuracy at Ranges Below 100A

±0.5A (combined linearity, hysteresis, and repeatability)****

Accuracy at Ranges Above 100A

±0.5% full scale (combined linearity, hysteresis, and repeatability)****

Withstand Current 25,000ADC

Response Time

H970: 2 sec; H971, EA20: Less than 150 msec

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage. For applications requiring double or reinforced insulation, please contact the factory.

* For currents over 120A, supply voltage must be at least 15V.

** For H971, at zero load current: 35mA max.; at 200A load current: 55mA to 100mA depending on supply voltage and current polarity.

*** Unless factory set per customer specifications (H971SP only).

**** For single conductor through product (no wraps).

pulse reset

technology™

U.S. Pat. #6,160,697; 6,522,517; 7,242,157

Year

Warranty

5

H971

FEATURES

All Models

Self-gripping iris for easy installation

Bracket can be installed in three different configurations...added flexibility

Status LED ensures proper wiring...easy set up

5-year warranty

H970 Multi-Output Model

Factory calibrated switch-selectable amp ranges (20/40/80 or 50/100/200) for

high resolution and installation ease

mA and DC voltage outputs...maximum installation flexibility

H971 Bidirectional Model

Patented Pulse Reset Technology™ significantly increases accuracy...sensor is

not affected by stray magnetic fields...minimize worry of magnetization from

over-current faults

User-adjustable span from ±20A to ±200A

Range can be factory-set per customer specifications (SP model)

EA20 Unidirectional Model

Patented Pulse Reset Technology™ significantly increases accuracy...sensor is

not affected by stray magnetic fields...minimize worry of magnetization from

over-current faults

100, 150, and 200A span versions available...application flexibility

DESCRIPTION

Hawkeye DC Sensors provide accurate load level monitoring of DC current loads. The

H970 combines a Hall Effect sensor with proven transducer circuitry. Slide-switch

selectable amperage ranges and field selectable mA and VDC outputs maximize

flexibility. The H971 uses Pulse Reset Technologywith field proven circuitry to

provide a superior solution for DC applications with minimal risk of permanent

magnetization, ensuring longer life and better accuracy.

The H970 has low and high current options with slide switch selectable amperage

ranges and a choice of 0-5V, 0-10V, or 4-20mA outputs. The EA20 and the H971 have

4-20mA output only. The H971 also offers bidirectional sensing capability and a

user-adjustable span to allow greater application flexibility.

APPLICATIONS

Battery chargers

Motor armature current

Motor field current

Automotive loads

Marine equipment

Solar energy applications

Telecom

Electroplating

H970, H971, & EA20 SERIES

TM

HQ0001768.C 01131

Advertising